| Plan Review Notes For Permit 23011338 |
| Permit Number |
23011338 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-02-10 06:56:27 | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | LOAD FOR CHARGER NOT SHOWN ON PLAN. | | | | | | OUTLET TO BE GFCI PROTECTED | | | | | | 625.54 GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION FOR | | | PERSONNEL. | | | | | | ALL SINGLE-PHASE RECEPTACLES INSTALLED FOR THE | | | CONNECTION OF ELECTRIC VEHICLE CHARGING THAT ARE RATED | | | 150 VOLTS TO GROUND OR LESS, AND 50 AMPERES OR LESS | | | SHALL HAVE GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION | | | FOR PERSONNEL. | | | | | | VALUE OF WORK SHOWN IS LOW FOR THE SCOPE OF WORK. |
|