| 2023-02-09 11:35:41 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT-23011309 |
| | 2/8/23 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET G101: PROVIDE PLUMBING FIXTURE CALCULATIONS IN |
| | COMPLIANCE WITH TABLE 403.1 FBC P. THE OCCUPANT LOAD |
| | SUMMARY SHOWS A MIXED OCCUPANCY OF ASSEMBLY, BUSINESS, |
| | AND DAYCARE. REFER TO SEC. 403.1.1: FRACTIONAL NUMBERS |
| | FOR EACH OCCUPANCY SHALL FIRST BE SUMMED AND ROUNDED UP |
| | TO THE NEXT WHOLE NUMBER. IT APPEARS A SINGLE UNISEX |
| | TOILET ROOM HAS BEEN PROVIDED FOR THE DAY CARE HOWEVER |
| | SEPARATE FACILITIES FOR MALE AND FEMALE USE ARE |
| | REQUIRED- SEC. 403.2 FBC P. PLEASE NOTE THE FOLLOWING |
| | FIXTURE CALCULATIONS FOR FEMALE USE. |
| | ASSEMBLY- 328 FEMALE OCCUPANTS AT 1 PER 65 = 5.05 WATER |
| | CLOSETS |
| | BUSINESS- 42 FEMALE OCCUPANTS AT 1 PER 25 = 1.68 WATER |
| | CLOSETS |
| | TOTAL- 6.73 ROUNDS UP TO 7 WATER CLOSETS REQUIRED. THE |
| | PLAN SHOWS 6 FEMALE WATER CLOSETS PROVIDED IN THE GANG |
| | BATHROOM WHICH IS A DEFICIENCY OF ONE. |
| | |
| | 2) P401: THE VENTS FOR THE URINALS (UR) SHALL NOT SERVE |
| | AS THE VENTS FOR THE WATER CLOSETS (W-1) ON EACH BRANCH |
| | BECAUSE THE URINALS ARE NOT FIXTURES INCLUDED IN A |
| | BATHROOM GROUP AND CANNOT NOT BE PART OF A WET VENT |
| | SYSTEM- SECS. 202 & 912.1 FBC P. PLEASE CHOSE ANOTHER |
| | VENTING METHOD SUCH AS INDIVIDUAL, COMMON, OR CIRCUIT |
| | VENTING- SECS. 910, 911, 914. |
| | |
| | 3) P401: PROVIDE AN INDIVIDUAL VENT FOR THE MOP SINK |
| | (MSB)- SEC. 910.1 FBC P. |
| | |
| | 4) P401: PLEASE SHOW THERE IS A VENT EXTENDING TO THE |
| | OUTDOORS FOR THE BUILDING DRAIN- SEC. 904.1 FBC P. |
| | |
| | 5) P401 & P801: THE RISER SHOWS 1/2-INCH FIXTURE SUPPLY |
| | PIPES FOR THE URINALS HOWEVER THE FIXTURE SCHEDULE |
| | SHOWS 3/4-INCH- TABLE 604.5 FBC P. SINCE THE RISER AND |
| | SCHEDULE EACH SHOW 1/2-INCH CW SUPPLY TO THE WATER |
| | CLOSETS, IT'SS IMPORTANT TO NOTE THAT THE |
| | OWNER-SUPPLIED WATER CLOSETS SHALL NOT BE EQUIPPED WITH |
| | FLUSH VALVES WHICH WOULD REQUIRE 1-INCH SUPPLY PIPES. |
| | |
| | 6) P401, P702: IN ORDER TO PROVIDE A MEANS OF LIMITING |
| | THE HOT WATER TEMPERATURE DELIVERY OTHER THAN THE WATER |
| | HEATER THERMOSTAT, A MASTER THERMOSTATIC MIXING VALVE |
| | SHALL BE PROVIDED- SEC. 607.1.1 FBC P. PLEASE SHOW THE |
| | LOCATION AND PIPING CONNECTIONS ON THE WATER HEATER |
| | DETAIL ON P702- SEC. 607.2.2 FBC P. |
| | A) PLEASE PROVIDE THE MISSING INFORMATION IN THE MIXING |
| | VALVE EQUIPMENT SCHEDULE ON SHEET P801 FOR THE TMV AND |
| | THE POINT OF USE VALVES AT THE HAND WASHING SINKS- |
| | SECS. 607.1.1 & 607.1.2 FBC P. |
| | |
| | 7) THE 1/2-INCH HW SUPPLY PIPES TO THE PUBLIC |
| | LAVATORIES SHALL NOT EXCEED 2FT. TO TERMINATION FROM |
| | THE HW SOURCE PER TABLE C404.5.1 FBC ENERGY. IN ORDER |
| | TO MEET COMPLIANCE, THE RECIRCULATION LINES MUST LOOP |
| | DOWN TO THE LAVATORIES OR POINT OF USE WATER HEATERS |
| | MUST BE PROVIDED. |
| | |
| | 8) P101, P201, P402: THE PLANS SHOW NEW SAUNAS. PLEASE |
| | NOTE IF THE SAUNAS ARE STEAM POWERED, THE STEAM UNITS |
| | WILL TYPICALLY REQUIRE WATER SUPPLY LINES, BACKFLOW |
| | PREVENTERS AND DRAINS- SEC. 107.2.1 WPB. |
| | |
| | 9) A201 & A420: PLEASE PROVIDE THE FOLLOWING ACCESSIBLE |
| | BATHROOM FIXTURE DETAILS PER THE FBC ACC. |
| | A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| | WATER CLOSETS- SEC. 604.3. |
| | B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| | LAVATORIES- SEC. 606.2. |
| | C) TURNING SPACES AT THE WATER CLOSETS- SEC. 304.3. |
| | D) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE |
| | WALLS- SEC. 604.2. |
| | E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED |
| | FLOORS- SEC. 604.4. |
| | F) HEIGHTS OF THE LAVATORY SINK RIMS OR COUNTER |
| | SURFACES FROM THE FINISHED FLOOR- SEC. 606.3. |
| | G) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO |
| | THE REFLECTIVE SURFACES- SEC. 603.3 |
| | H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| | BARS FOR THE WATER CLOSETS IN THE WHEELCHAIR |
| | COMPARTMENTS AND THE AMBULATORY COMPARTMENTS- SECS. |
| | 604.5, 604.8.2.3 & 609.4, |
| | I) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS- SEC. |
| | 604.6. |
| | J) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED |
| | FROM THE FRONTS OF THE WATER CLOSETS- SEC. AND FIGURE |
| | 604.7. |
| | K) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SEC. |
| | 606.2. |
| | L) HEIGHT OF THE URINAL RIM FROM THE FINISHED FLOOR AND |
| | DEPTH FROM THE RIM TO THE BACK OF THE FIXTURE- SEC. |
| | 605.2. |
| | M) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| | ROLL-IN SHOWERS- SEC. 608.2.2. |
| | N) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| | BARS FOR THE ROLL-IN SHOWER- SECS. 608.3.2 & 609.4. |
| | O) LOCATION OF CONTROL, FAUCET, AND SHOWER SPRAY IN THE |
| | SHOWER- SEC. 608.5.2. |
| | |
| | 10) A102, P101, & P801: PLEASE NOTE THE FUTURE |
| | BREAKROOM SINK (S-1) SHALL BE ACCESSIBLE PER SEC. 606.2 |
| | FBC ACC. THE SCHEDULE ON P801 LISTS IT AS NON-ADA. |
| | REFER TO SEC. 606.2 & 606.3 FBC ACC AND PROVIDE |
| | DETAILS. |
| | |
| | 11) A201: PLEASE DETAIL ACCESSIBLE DRINKING FOUNTAIN |
| | COMPLIANCES PER ITEMS A, B, & C- FBC ACC. |
| | A) CLEAR FLOOR SPACE APPROACH DIAGRAM AND DIMENSIONS |
| | FOR THE WHEELCHAIR ACCESSIBLE FOUNTAIN - SEC. 602.2. |
| | B) KNEE AND TOE CLEARANCES FOR THE WHEELCHAIR |
| | ACCESSIBLE FOUNTAIN- SEC. 602.2. |
| | C) SPOUT HEIGHTS FOR THE WHEELCHAIR ACCESSIBLE FOUNTAIN |
| | AND THE FOUNTAIN FOR STANDING PERSONS- SEC. 602.4 & |
| | 602.7. |
| | |
| | 12) A201 & P801: THE DRINKING FOUNTAINS SHALL NOT |
| | PROTRUDE INTO THE CIRCULATION PATH PER SEC. 307.2 FBC |
| | ACC. SINCE THE FOUNTAINS ARE OWNER SELECTED IT'S |
| | IMPORTANT TO NOTE THAT SOME FOUNTAINS ARE EQUIPPED WITH |
| | APRONS FOR CANE SWEEP, WHEREAS OTHERS WITHOUT APRONS |
| | MUST BE INSTALLED IN A NICHE OR GUARDED IN SOME WAY. |
| | |
| | 13) A201 & A420: PLEASE PROVIDE THE WIDTHS OF THE |
| | STANDARD WATER CLSOETS IN THE GANG BATHROOMS- SEC. |
| | 405.3.1 FBC P. |
| | |
| | 14) CONCERNING THE DAYCARE TOILET ROOM PLEASE REFER TO |
| | SEC. 604.1 FBC ACC. IF THE EXCEPTION UNDER 604.1 IS |
| | BEING CLAIMED, PLEASE PROVIDE DETAILS SHOWING |
| | COMPLIANCE WITH WATER CLOSET SPECIFICATIONS FOR |
| | CHILDREN'S USE 604.9- 609.9.7 FBC ACC. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |