| 2023-02-14 09:27:34 | 1ST REVIEW FMC |
| | PERMIT: 23011309 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE THE MECHANICAL EQUIPMENT SIZING |
| | CALCULATIONS. FEC C403.2.1 |
| | |
| | 2) THE ENERGY CALCULATIONS INDICATE 5 SYSTEMS BUT SHEET |
| | M002 INDICATES A TOTAL OF 16 RTU???S. PROVIDE AN ENERGY |
| | CALCULATION THAT MATCHES THE MECHANICAL DESIGN OF THIS |
| | TENANT. FBC 107.3.5 |
| | |
| | 3) THE MECHANICAL SHEETS INDICATE SEVERAL SUPPLY |
| | GRILLES WITH THE OUTDOOR AIR CFM???S. WHAT IS THIS? |
| | ISN???T THE RTU???S SUPPLYING THE REQUIRED OUTDOOR AIR |
| | TO EACH ZONE? |
| | |
| | 4) IDENTIFY THE RTU???S ON EACH ZONE DRAWING. FBC |
| | 107.3.5 |
| | |
| | 5) PROVIDE A COMPLETE DESIGN INCLUDING ALL DUCT WORK |
| | FROM THE 16 RTU???S. ZONE A ONLY SHOWS 2 AREAS WITH |
| | DUCT WORK AND ZONE B ONLY SHOWS 1 AREA. FBC 107.3.5 |
| | |
| | 6) SHEET M801: OUTDOOR AIR CALCULATIONS: FMC 403.3.1.1 |
| | AND TABLE 403.3.1.1 |
| | |
| | A) THE LOBBY SHOULD BE CALCULATED FOR 15 PEOPLE AND NOT |
| | 11. |
| | B) THE MAIN GYM AREA IS STATING A TOTAL OF 215 |
| | OCCUPANTS. 200 OCC. X 20 CFM???S PER OCCUPANT = 4300 |
| | CFM???S. 21450 X 0.18 = 3,861 CFM???S FOR THE SPACE; |
| | 4300 + 3861 = REQUIRED OUTDOOR AIR FOR THIS SPACE IS |
| | 8,161 CFM???S |
| | C) THE COURT IS STATING 24 OCCUPANTS. 24 X 20 = 480 |
| | CFM???S PER OCCUPANT. 2460 X 0.18 = 442.8; REQUIRED |
| | CFM???S OF OUTDOOR AIR FOR THIS SPACE IS 480 + 442.8 = |
| | 923 CFM???S. |
| | D) THE WOMEN???S EXERCISE ROOM REQUIRED OUTDOOR AIR |
| | SHOULD BE CALCULATED FOR 36 OCCUPANTS. |
| | 36 OCCUPANTS X 20 = 720 CFM???S; 880 X 0.06 = 52.8 |
| | CFM???S FOR THIS SPACE. 720 + 53 = 773 CFM???S |
| | REQUIRED. |
| | E) THE GROUP EXERCISE ROOM???S REQUIRED OUTDOOR AIR |
| | SHOULD BE CALCULATED FOR 38 OCCUPANTS. |
| | 38 X 20 = 760 CFM???S PER OCCUPANT; 945 X 0.06 = 56.7 |
| | CFM???S REQUIRED FOR THE SPACE; 760 + 56.7 = 817 |
| | CFM???S REQUIRED. |
| | |
| | 7) PROVIDE A DRAWING WITH THE EXHAUST FANS, COMPLETE |
| | DUCTWORK AND TERMINATION LOCATION. FBC 107.3.5 |
| | |