Plan Review Notes
Plan Review Notes For Permit 23011309
Permit Number 23011309
Review Stop M
Sequence Number 1
Notes
Date Text
2023-02-14 09:27:341ST REVIEW FMC
 PERMIT: 23011309
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS. FEC C403.2.1
  
 2) THE ENERGY CALCULATIONS INDICATE 5 SYSTEMS BUT SHEET
 M002 INDICATES A TOTAL OF 16 RTU???S. PROVIDE AN ENERGY
 CALCULATION THAT MATCHES THE MECHANICAL DESIGN OF THIS
 TENANT. FBC 107.3.5
  
 3) THE MECHANICAL SHEETS INDICATE SEVERAL SUPPLY
 GRILLES WITH THE OUTDOOR AIR CFM???S. WHAT IS THIS?
 ISN???T THE RTU???S SUPPLYING THE REQUIRED OUTDOOR AIR
 TO EACH ZONE?
  
 4) IDENTIFY THE RTU???S ON EACH ZONE DRAWING. FBC
 107.3.5
  
 5) PROVIDE A COMPLETE DESIGN INCLUDING ALL DUCT WORK
 FROM THE 16 RTU???S. ZONE A ONLY SHOWS 2 AREAS WITH
 DUCT WORK AND ZONE B ONLY SHOWS 1 AREA. FBC 107.3.5
  
 6) SHEET M801: OUTDOOR AIR CALCULATIONS: FMC 403.3.1.1
 AND TABLE 403.3.1.1
  
 A) THE LOBBY SHOULD BE CALCULATED FOR 15 PEOPLE AND NOT
 11.
 B) THE MAIN GYM AREA IS STATING A TOTAL OF 215
 OCCUPANTS. 200 OCC. X 20 CFM???S PER OCCUPANT = 4300
 CFM???S. 21450 X 0.18 = 3,861 CFM???S FOR THE SPACE;
 4300 + 3861 = REQUIRED OUTDOOR AIR FOR THIS SPACE IS
 8,161 CFM???S
 C) THE COURT IS STATING 24 OCCUPANTS. 24 X 20 = 480
 CFM???S PER OCCUPANT. 2460 X 0.18 = 442.8; REQUIRED
 CFM???S OF OUTDOOR AIR FOR THIS SPACE IS 480 + 442.8 =
 923 CFM???S.
 D) THE WOMEN???S EXERCISE ROOM REQUIRED OUTDOOR AIR
 SHOULD BE CALCULATED FOR 36 OCCUPANTS.
 36 OCCUPANTS X 20 = 720 CFM???S; 880 X 0.06 = 52.8
 CFM???S FOR THIS SPACE. 720 + 53 = 773 CFM???S
 REQUIRED.
 E) THE GROUP EXERCISE ROOM???S REQUIRED OUTDOOR AIR
 SHOULD BE CALCULATED FOR 38 OCCUPANTS.
 38 X 20 = 760 CFM???S PER OCCUPANT; 945 X 0.06 = 56.7
 CFM???S REQUIRED FOR THE SPACE; 760 + 56.7 = 817
 CFM???S REQUIRED.
  
 7) PROVIDE A DRAWING WITH THE EXHAUST FANS, COMPLETE
 DUCTWORK AND TERMINATION LOCATION. FBC 107.3.5
  