Plan Review Notes
Plan Review Notes For Permit 23011309
Permit Number 23011309
Review Stop B
Sequence Number 1
Notes
Date Text
2023-02-14 09:17:37WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING AUDIT
 W. P. B. PERMIT: 23011309
 ADD: 2751 S. DIXIE HWY.
 CONT: DABAZZO DEVELOPMENT
 TEL: 727-220-6940
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. FEB.13TH/ 2023
 ACTION: DENIED
  
 1) IT APPEARS A SITE PLAN IS NEEDED OR KEY PLAN
 INDICATING THE LOCATION OF THIS TENANT SPACE WITHIN THE
 BUILDING, THE LIFE SAFETY BUILDING INFORMATION STATES
 STRIP CENTER DEMISING WALLS/ OTHER TENANTS??? EAST
 SIDE, WEST SIDE NORTH (FRONT) AND SOUTH OPEN 2 SIDES OF
 BUILDING. IT APPEARS EITHER THIS IS A SITE ADDRESS OR
 UNIT ADDRESS. AN ADDRESSING STOP WILL BE ADDED TO THE
 PLAN REVIEW TEAM. 2020 WEST PALM BEACH AMENDMENTS TO
 THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 107.2.1. CONSTRUCTION DOCUMENTS SHALL BE SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL.
 2020 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED.
  
 2) SITE PLAN OR KEY PLAN WILL NEED TO INDICATE THE TYPE
 OF OCCUPANCIES THAT ADJOIN THIS A-3 OCCUPANCY TO
 CLARIFY OCCUPANCY SEPARATION PER TABLE 508.4 OF THE
 2020FBC-BUILDING CODE.
  
 3) MISSING INFORMATION, THE WIDTH AND OVERALL LENGTH OF
 NEW FRONT STAIRWAY AND RAMP, AND SIDE RAMP. WIDTH AND
 LENGTH. NOT FOUND ON THE LIFE SAFETY PLAN, A-102 A
 ZONE, A-103 B ZONE, A-103 OR S-2.0 FOUNDATION PLAN.
 2020 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.2.1. CONSTRUCTION
 DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
  
 4) THE LIFE SAFETY FLOOR PLAN STATES THE OCCUPANCY LOAD
 FOR THIS TENANT SPACE GIVE DIFFERENT NARRATIVES ON THE
 OCCUPANT LOAD FBC 2020 398, NFPA A-101 398 ACTUAL
 PROVIDED 495 BUT THEN BELOW OCCUPANT LOAD SUMMARY 796
 OCCUPANT LOAD, A GREAT DIFFERENCE PLEASE INDICATE OF
 THE 4 OCCUPANT LOADS STATED WHICH IS YOUR DESIGN BASED
 UPON, WE USE THE MOST RESTRICTIVE. THE LIFE SAFETY PLAN
 SHOULD PROVIDE THE MAXIMUM OCCUPANT LOAD THAT CAN GO
 OUT THROUGH THE DOOR WHEN OPEN AT 90 DEGREES, AND OUT
 THE STAIRS AND RAMPS NOT FOUND ON THIS PLAN. 2020
 FBC-BUILDING CODE SECTION 1005 MEANS OF EGRESS,
 1005.3.1 STAIRS & 1005.3.2 OTHER MEANS OF EGRESS
 COMPONENTS PLEASE PROVIDE THE EGRESS CAPACITY FACTOR
 FOR DOORWAYS, STAIRS & RAMPS PROPOSED AND EXISTING.
  
 5) THIS PORTION OF THE BUILDING IS TO BE CLASSIFIED AS
 AN THRESHOLD BUILDING, FL. S. S. 553.71 (7) ANY
 BUILDING WHICH HAS AN ASSEMBLY OCCUPANCY WHICH EXCEEDS
 5,000 SQ. FT. IN AREA AND AN OCCUPANT CONTENT OF
 GREATER THAN 500 PERSONS, AS STATED ON PLAN 796
 OCCUPANTS.
  
 5A) 109.3.6.1 THRESHOLD INSPECTION PLAN. THE ENFORCING
 AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 5B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS
 ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH
 INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND
 REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE
 PLACE.
  
 5C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B.
 AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 5D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
  
 5E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 6) THE LIFE SAFETY SHEET G101 STATES THE SCALE OF THE
 DRAWINGS IS 1/16??? = 1 FOOT. 107.2.1.3. QUALITY OF
 PLANS. BUILDING PLANS SHALL BE DRAWN TO A 1/8TH INCH
 SCALE ON SUBSTANTIAL PAPER. THE BUILDING OFFICIAL MAY
 ESTABLISH THROUGH DEPARTMENT POLICY OTHER STANDARDS FOR
 THE PLANS AND SPECIFICATIONS IN ORDER TO PROVIDE
 CONFORMITY TO ITS RECORD RETENTION PROGRAM. THIS POLICY
 MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, SHAPE,
 CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO RECORD
 MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE WITH
 THE ARCHIVE REQUIREMENTS OF FLORIDA STATUTES.
  
 7A) SHEET A103 ZONE B DOES NOT PROVIDE THE LANDING
 WIDTH. SHEET A-201 WIDTH AND LENGTH OF THE TOP LANDING
 TO BE 5 FEET 0 ?? INCHES BY 5 FEET 0 ?? INCHES. PLEASE
 PROVIDE THE 5-FOOT TURNING RADIUS ON THE PLAN, IT
 APPEARS IT WILL GO BENEATH THE GUARDRAIL SYSTEM AS
 DESIGNED. SHOW COMPLIANCE WITH THE 2020 FBC-ACCESS.
 CODE 304.3.1 CIRCULAR SPACE, THE SPACE SHALL BE
 PERMITTED TO INCLUDE KNEE & TOE CLEARANCES COMPLYING
 WITH 306.
  
 7B) THE PROPOSED RAMP LANDING AND EXIT SIDE DOOR, THE
 EXIT SIDE DOOR NEEDS TO COMPLY WITH 2020 FBC-ACCESS.
 CODE SECTION 405.7.5 & FIGURE 404.2.4.1(J) 24-INCH
 MINIMUM MANEUVERING CLEARANCE BEFORE THE START OF THE
 RAMP.
  
 7C) SHEET A300 DETAIL 2 SIDE RAMP DETAIL OF HANDRAIL/
 GUARDRAIL. TYPO INTERMEDIATE RAILS AT 4 INCHES ON
 CENTER VERTICALLY, SHOULD READ HORIZONTALLY. TYPO.
 ADDITIONAL INFORMATION REQUIRED. 107.2.1.2.
  
 7D) SHEET A300 DETAIL 4 PROPOSED FRONT EXTERIOR STAIR.
 THE DETAIL OF GUARD AND HANDRAIL DOES NOT SHOW THE
 HORIZONTAL EXTENSION OF THE HANDRAIL IN ACCORDANCE WITH
 1014.6 HANDRAIL EXTENSIONS.
  
 7E) SHEET A300 DETAIL 5 BOTH HANDRAILS AGAINST THE WALL
 ARE MISSING THE HORIZONTAL EXTENSION MISSING COMPLIANCE
 WITH 1014.6 OF THE 2020 FBC-BUILDING CODE. REVIEW THE
 WALL HANDRAIL OF THE STAIR, NOT ONLY MISSING THE
 EXTENSION STOPS SHORT AT THE TOP OF THE FIRST RISER, IT
 DOES NOT CONTINUE ON THE SLOPE FOR THE DEPTH OF ONE
 TREAD BEYOND THE BOTTOM RISER, 2020 FBC-BUILDING
 SECTION 1014.6.
  
 7F) SHEET A300 DETAIL 6 HANDRAILS AGAINST THE WALL ARE
 MISSING THE HORIZONTAL EXTENSION MISSING COMPLIANCE
 WITH 1014.6 OF THE 2020 FBC-BUILDING CODE.
  
 8) SHEET A-201 AT THE BOTTOM LEFT OF SHEET PLEASE
 PROVIDE EITHER A DETAIL OR CUT SECTION FOR THE INFILL
 OF PROPOSED FLOOR SLAB, SOIL TREATMENT PER 1816.1.4 AND
 DOWELING/ REINFORCEMENT OF SLAB. MISSING DETAIL.
 107.2.1. 2020 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION 107.2.1.
 CONSTRUCTION DOCUMENTS SHALL BE SUFFICIENT CLARITY TO
 INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 9A) SHEET A104 ROOF PLAN, NOR M103 OR M104 SHOW ACCESS
 TO THE ROOF FOR ROOF TOP AIR HANDLERS. 2020 FBC-M 306.5
 EQUIPMENT AND APPLIANCES ON ROOFS OR ELEVATED
 STRUCTURES.
 2020 FBC-M 306.5 EQUIPMENT AND APPLIANCES ON ROOFS OR
 ELEVATED STRUCTURES. WHERE EQUIPMENT REQUIRING ACCESS
 OR APPLIANCES ARE LOCATED ON AN ELEVATED STRUCTURE OR
 THE ROOF OF A BUILDING SUCH THAT PERSONNEL WILL HAVE TO
 CLIMB HIGHER THAN 16 FEET ABOVE GRADE TO ACCESS SUCH
 EQUIPMENT OR APPLIANCES, AN INTERIOR OR EXTERIOR MEANS
 OF ACCESS SHALL BE PROVIDED. SUCH ACCESS SHALL NOT
 REQUIRE CLIMBING OVER OBSTRUCTIONS GREATER THAN 30
 INCHES IN HEIGHT OR WALKING ON ROOFS HAVING A SLOPE
 GREATER THAN 4 UNITS VERTICAL IN 12 UNITS HORIZONTAL
 (33-PERCENT SLOPE). SUCH ACCESS SHALL NOT REQUIRE THE
 USE OF PORTABLE LADDERS. WHERE ACCESS INVOLVES CLIMBING
 OVER PARAPET WALLS, THE HEIGHT SHALL BE MEASURED TO THE
 TOP OF THE PARAPET WALL.
  
 9B) ROOF TOP HATCHES/ ROOF ACCESS/ 2020 FBC-B
 1011.12.2. IN BUILDINGS THAT DO NOT HAVE AN OCCUPIED
 ROOF SHALL BE PERMITTED TO BE A ROOF HATCH OR TRAP DOOR
 NOT LESS THAN 16 SQUARE FEET IN AREA AND HAVING A
 MINIMUM DIMENSION OF 2 FEET.
 OR
 9B) 2020 FBC-B 1011.16 LADDERS. PERMANENT LADDERS SHALL
 NOT SERVE AS A PART OF THE MEANS OF EGRESS FROM
 OCCUPIED SPACES WITHIN A BUILDING. PERMANENT LADDERS
 SHALL BE PERMITTED TO PROVIDE ACCESS TO THE FOLLOWING
 AREAS:
 1.SPACES FREQUENTED ONLY BY PERSONNEL FOR MAINTENANCE,
 REPAIR OR MONITORING OF EQUIPMENT.
 5.NONOCCUPIED ROOFS THAT ARE NOT REQUIRED TO HAVE
 STAIRWAY ACCESS IN ACCORDANCE WITH SECTION
 1011.12.1.
 6.LADDERS SHALL BE CONSTRUCTED IN ACCORDANCE WITH
 SECTION 306.5 OF THE FLORIDA BUILDING CODE,
 MECHANICAL.
  
 10) SHEET A201:
 10A) THE FLOOR PLAN SHOWS THE HIGH-LOW DRINKING
 FOUNTAINS BUT NOT COMPLIANCE WITH:
  
 10A)(1) PROTRUDING OBJECTS 307.2 PROTRUSION LIMITS
 307.2. OBJECTS WITH LEADING EDGES MORE THAN 27 INCHES
 AND NOT MORE THAN 80 INCHES ABOVE THE FLOOR SHALL NOT
 PROTRUDE MORE THAN 4 INCHES HORIZONTALLY INTO THE
 CIRCULATION PATH.
  
 10A)(2) 602.2 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE
 COMPLYING WITH 305, POSITIONED FOR A FORWARD APPROACH,
 AND KNEE AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE
 PROVIDED.
  
  
 10A)(3) SPOUT OUTLETS/ DRINKING FOUNTAINS. 2017 ACCESS.
 CODE. SPOUT OUTLETS SHALL COMPLY WITH:
 602.4 SPOUT HEIGHT. 36 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND FOR WHEELCHAIR BOUND INDIVIDUALS.
 602.7 SPOUT HEIGHT FOR THE STANDING PERSONS SHALL BE
 BETWEEN 38 TO 43 INCHES ABOVE FINISH FLOOR.
  
 10B) JANITORS CLOSET # 120 WITH MOP SINK FINISH
 SCHEDULE FOR WALLS INDICATES WALL PAINT FINISH A601.
 2020 FBC-B 1210.2.2. WALLS & PARTITIONS. THIS COMMENT
 IS A RESULT OF THE BUILDING OFFICIAL INTERPRETATION ON
 06/2020. IN BATHROOMS, RESTROOMS & SERVICE SINK AREAS
 EPOXY PAINT IS NO LONGER CONSIDERED A SMOOTH HARD,
 NON-ABSORBENT SURFACE.
  
 10C) BATHROOMS 111,121 & 123 ON THE FINISH SCHEDULE
 (A601) INDICATE PAINT FINISH. 2020 FBC-B 1210.2.2.
 WALLS & PARTITIONS. THIS COMMENT IS A RESULT OF THE
 BUILDING OFFICIAL INTERPRETATION ON 06/2020. IN
 BATHROOMS, RESTROOMS & SERVICE SINK AREAS EPOXY PAINT
 IS NO LONGER CONSIDERED A SMOOTH HARD, NON-ABSORBENT
 SURFACE.
  
 10D) 2020 FBC-B 2509.2 BASE FOR TILE. MATERIALS USED AS
 A BASE FOR WALL TILE IN TUB AND SHOWER AREAS AND WALLS
 AND CEILING PANELS IN SHOWER AREAS SHALL BE OF
 MATERIALS LISTED IN TABLE 2509.2 AND INSTALLED IN
 ACCORDANCE WITH MANUFACTURER???S RECOMMENDATIONS. WATER
 RESISTANT GYPSUM (MR BOARD) SHALL NOT BE USED FOR
 SHOWER & TUB ENCLOSURES BUT CAN BE USED FOR BACKING
 BOARD FOR A BASE FOR TILE IN WATER CLOSET COMPARTMENT
 WALLS WHEN INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM
 C840 AND THE MANUFACTURE???S RECOMMENDATIONS.
  
 10E) 2509.1. WET AREAS. SHOWERS AND PUBLIC TOILET WALLS
 SHALL COMPLY WITH 1210.2.
  
 11) SHEET A601 ACCESSIBLE DETAILS:
  
 11A) DETAILS ARE SHOWN FOR TOILET PARTITIONS BUT LAV
 NOT INCLUDED IN THE TOILET STALL, DISCREPANCY FROM THE
 FLOOR PLAN A102, NOT SHOWING COMPLIANCE WITH 2020
 FBC-ACCESSIBILITY CODE SECTION 604.3.1 & FIGURE 604.3.1
 CLEARANCE AT WATER CLOSETS. THE 2020 FBC-ACCESSIBILITY
 CODE SECTION 604.3.1 & FIGURE 604.3.1 CLEARANCE AT
 WATER CLOSETS AND OVERLAP IN SECTION 604.3.2.
  
 11B) HEIGHT OF GRAB BARS. GRAB BARS/ RESTROOMS. 2020
 FBC-ACCESSIBILITY CODE SECTION 609.4 POSITION OF GRAB
 BARS. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION, 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING
 SURFACE, NOT CENTERLINE.
  
 11C) URINAL HEIGHT FOR STANDARD, TYPO CAN NOT READ.
 107.2.1. ADDITIONAL INFORMATION IS REQUIRED.
  
 11D) SHEET A102 TOILET ROOM 111 WITH INSWING DOOR DOES
 NOT SHOW MANEUVERING CLEARANCES 2020 FBC-ACCESSIBILITY
 CODE SECTION 604.3.1 & FIGURE 604.3.1 CLEARANCE AT
 WATER CLOSETS. THE 2020 FBC-ACCESSIBILITY CODE SECTION
 604.3.1 & FIGURE 604.3.1 CLEARANCE AT WATER CLOSETS AND
 OVERLAP IN SECTION 604.3.2.
  
 11E) TOILET ROOM DOORS. 2020 FBC-ACCESSIBILITY CODE
 PLEASE REVIEW SECTION 603.2.3. DOORS SHALL NOT SWING
 INTO THE CLEAR FLOOR SPACE OR CLEARANCES REQUIRED FOR
 ANY FIXTURE. DOORS SHALL BE PERMITTED TO SWING INTO THE
 REQUIRED TURNING SPACE. PLEASE SEE EXCEPTION 2. WHERE
 TOILET ROOMS ARE FOR INDIVIDUAL USE AND A CLEAR FLOORS
 SPACE COMPLYING WITH 305.3 IS PROVIDED WITHIN THE ROOM
 BEYOND THE ARC OF THE DOOR SWING. WHAT IS MISSING IS
 THE REQUIRED 30X48 INCH CLEAR FLOOR SPACE BEYOND THE
 ARC OF THE DOOR. USUALLY AT A 45% ANGLE TO THE DOOR
 ENTRANCE.
  
 12) SHEET A102 ROOM 116 THE BREAK ROOM THERE ARE NO
 DETAIL IF THERE IS COUNTERS AND CHAIRS.
  
 12)(A) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 12)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 13) SHEET A101 SHOWS THE LOBBY WITH RECEPTION DESK BUT
 NO DETAIL SHOWING COMPLIANCE WITH THE 2020 FL
 ACCESSIBILITY CODE SECTIONS: CHECK WRITING SURFACES.
 2020 ACCESS. CODE 904.3.3 CHECK WRITING SURFACES. WHERE
 PROVIDED, CHECK WRITING SURFACES SHALL COMPLY WITH
 902.3HEIGHT. THE TOPS OF WORK SURFACES SHALL BE 28
 INCHES MINIMUM AND 34 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 14) SHEETS A101 & A102 ARE MISSING COMPLIANCE WITH THE
 2020 FBC-ACCESSIBILITY CODE SECTION 1004. 1. CLEAR
 FLOOR SPACE FOR EXERCISE MACHINES AND EQUIPMENT.
  
 15) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT
 REMARKS MAYBE MADE IN THE NEXT REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  