| 2023-02-14 09:17:37 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2020 FBC- BUILDING AUDIT |
| | W. P. B. PERMIT: 23011309 |
| | ADD: 2751 S. DIXIE HWY. |
| | CONT: DABAZZO DEVELOPMENT |
| | TEL: 727-220-6940 |
| | E-MAIL: [email protected] |
| | |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. FEB.13TH/ 2023 |
| | ACTION: DENIED |
| | |
| | 1) IT APPEARS A SITE PLAN IS NEEDED OR KEY PLAN |
| | INDICATING THE LOCATION OF THIS TENANT SPACE WITHIN THE |
| | BUILDING, THE LIFE SAFETY BUILDING INFORMATION STATES |
| | STRIP CENTER DEMISING WALLS/ OTHER TENANTS??? EAST |
| | SIDE, WEST SIDE NORTH (FRONT) AND SOUTH OPEN 2 SIDES OF |
| | BUILDING. IT APPEARS EITHER THIS IS A SITE ADDRESS OR |
| | UNIT ADDRESS. AN ADDRESSING STOP WILL BE ADDED TO THE |
| | PLAN REVIEW TEAM. 2020 WEST PALM BEACH AMENDMENTS TO |
| | THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION |
| | 107.2.1. CONSTRUCTION DOCUMENTS SHALL BE SUFFICIENT |
| | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF |
| | THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| | CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT |
| | LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED |
| | BY THE BUILDING OFFICIAL. |
| | 2020 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE |
| | OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE |
| | AND EXTENT OF THE WORK PROPOSED. |
| | |
| | 2) SITE PLAN OR KEY PLAN WILL NEED TO INDICATE THE TYPE |
| | OF OCCUPANCIES THAT ADJOIN THIS A-3 OCCUPANCY TO |
| | CLARIFY OCCUPANCY SEPARATION PER TABLE 508.4 OF THE |
| | 2020FBC-BUILDING CODE. |
| | |
| | 3) MISSING INFORMATION, THE WIDTH AND OVERALL LENGTH OF |
| | NEW FRONT STAIRWAY AND RAMP, AND SIDE RAMP. WIDTH AND |
| | LENGTH. NOT FOUND ON THE LIFE SAFETY PLAN, A-102 A |
| | ZONE, A-103 B ZONE, A-103 OR S-2.0 FOUNDATION PLAN. |
| | 2020 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION 107.2.1. CONSTRUCTION |
| | DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE |
| | LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND |
| | SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS |
| | OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND |
| | REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | 4) THE LIFE SAFETY FLOOR PLAN STATES THE OCCUPANCY LOAD |
| | FOR THIS TENANT SPACE GIVE DIFFERENT NARRATIVES ON THE |
| | OCCUPANT LOAD FBC 2020 398, NFPA A-101 398 ACTUAL |
| | PROVIDED 495 BUT THEN BELOW OCCUPANT LOAD SUMMARY 796 |
| | OCCUPANT LOAD, A GREAT DIFFERENCE PLEASE INDICATE OF |
| | THE 4 OCCUPANT LOADS STATED WHICH IS YOUR DESIGN BASED |
| | UPON, WE USE THE MOST RESTRICTIVE. THE LIFE SAFETY PLAN |
| | SHOULD PROVIDE THE MAXIMUM OCCUPANT LOAD THAT CAN GO |
| | OUT THROUGH THE DOOR WHEN OPEN AT 90 DEGREES, AND OUT |
| | THE STAIRS AND RAMPS NOT FOUND ON THIS PLAN. 2020 |
| | FBC-BUILDING CODE SECTION 1005 MEANS OF EGRESS, |
| | 1005.3.1 STAIRS & 1005.3.2 OTHER MEANS OF EGRESS |
| | COMPONENTS PLEASE PROVIDE THE EGRESS CAPACITY FACTOR |
| | FOR DOORWAYS, STAIRS & RAMPS PROPOSED AND EXISTING. |
| | |
| | 5) THIS PORTION OF THE BUILDING IS TO BE CLASSIFIED AS |
| | AN THRESHOLD BUILDING, FL. S. S. 553.71 (7) ANY |
| | BUILDING WHICH HAS AN ASSEMBLY OCCUPANCY WHICH EXCEEDS |
| | 5,000 SQ. FT. IN AREA AND AN OCCUPANT CONTENT OF |
| | GREATER THAN 500 PERSONS, AS STATED ON PLAN 796 |
| | OCCUPANTS. |
| | |
| | 5A) 109.3.6.1 THRESHOLD INSPECTION PLAN. THE ENFORCING |
| | AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL |
| | INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A |
| | THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION |
| | PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL |
| | INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING |
| | AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR |
| | THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE |
| | OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE |
| | SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT |
| | THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE |
| | WITH THE PERMITTED DOCUMENTS. |
| | |
| | 5B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B. |
| | CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD |
| | BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S |
| | 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS |
| | REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS |
| | ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH |
| | INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND |
| | REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE |
| | PLACE. |
| | |
| | 5C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B. |
| | AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH |
| | ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT |
| | OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE |
| | BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE |
| | PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE |
| | FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL |
| | AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 |
| | FLORIDA STATUTE. |
| | |
| | 5D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME' |
| | OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE |
| | RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS |
| | SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE |
| | WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, |
| | AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| | WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| | MEETING THE ABOVE CRITERIA. |
| | |
| | 5E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR |
| | HISTORY FOR THIS TYPE OF CONSTRUCTION. |
| | |
| | 6) THE LIFE SAFETY SHEET G101 STATES THE SCALE OF THE |
| | DRAWINGS IS 1/16??? = 1 FOOT. 107.2.1.3. QUALITY OF |
| | PLANS. BUILDING PLANS SHALL BE DRAWN TO A 1/8TH INCH |
| | SCALE ON SUBSTANTIAL PAPER. THE BUILDING OFFICIAL MAY |
| | ESTABLISH THROUGH DEPARTMENT POLICY OTHER STANDARDS FOR |
| | THE PLANS AND SPECIFICATIONS IN ORDER TO PROVIDE |
| | CONFORMITY TO ITS RECORD RETENTION PROGRAM. THIS POLICY |
| | MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, SHAPE, |
| | CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO RECORD |
| | MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE WITH |
| | THE ARCHIVE REQUIREMENTS OF FLORIDA STATUTES. |
| | |
| | 7A) SHEET A103 ZONE B DOES NOT PROVIDE THE LANDING |
| | WIDTH. SHEET A-201 WIDTH AND LENGTH OF THE TOP LANDING |
| | TO BE 5 FEET 0 ?? INCHES BY 5 FEET 0 ?? INCHES. PLEASE |
| | PROVIDE THE 5-FOOT TURNING RADIUS ON THE PLAN, IT |
| | APPEARS IT WILL GO BENEATH THE GUARDRAIL SYSTEM AS |
| | DESIGNED. SHOW COMPLIANCE WITH THE 2020 FBC-ACCESS. |
| | CODE 304.3.1 CIRCULAR SPACE, THE SPACE SHALL BE |
| | PERMITTED TO INCLUDE KNEE & TOE CLEARANCES COMPLYING |
| | WITH 306. |
| | |
| | 7B) THE PROPOSED RAMP LANDING AND EXIT SIDE DOOR, THE |
| | EXIT SIDE DOOR NEEDS TO COMPLY WITH 2020 FBC-ACCESS. |
| | CODE SECTION 405.7.5 & FIGURE 404.2.4.1(J) 24-INCH |
| | MINIMUM MANEUVERING CLEARANCE BEFORE THE START OF THE |
| | RAMP. |
| | |
| | 7C) SHEET A300 DETAIL 2 SIDE RAMP DETAIL OF HANDRAIL/ |
| | GUARDRAIL. TYPO INTERMEDIATE RAILS AT 4 INCHES ON |
| | CENTER VERTICALLY, SHOULD READ HORIZONTALLY. TYPO. |
| | ADDITIONAL INFORMATION REQUIRED. 107.2.1.2. |
| | |
| | 7D) SHEET A300 DETAIL 4 PROPOSED FRONT EXTERIOR STAIR. |
| | THE DETAIL OF GUARD AND HANDRAIL DOES NOT SHOW THE |
| | HORIZONTAL EXTENSION OF THE HANDRAIL IN ACCORDANCE WITH |
| | 1014.6 HANDRAIL EXTENSIONS. |
| | |
| | 7E) SHEET A300 DETAIL 5 BOTH HANDRAILS AGAINST THE WALL |
| | ARE MISSING THE HORIZONTAL EXTENSION MISSING COMPLIANCE |
| | WITH 1014.6 OF THE 2020 FBC-BUILDING CODE. REVIEW THE |
| | WALL HANDRAIL OF THE STAIR, NOT ONLY MISSING THE |
| | EXTENSION STOPS SHORT AT THE TOP OF THE FIRST RISER, IT |
| | DOES NOT CONTINUE ON THE SLOPE FOR THE DEPTH OF ONE |
| | TREAD BEYOND THE BOTTOM RISER, 2020 FBC-BUILDING |
| | SECTION 1014.6. |
| | |
| | 7F) SHEET A300 DETAIL 6 HANDRAILS AGAINST THE WALL ARE |
| | MISSING THE HORIZONTAL EXTENSION MISSING COMPLIANCE |
| | WITH 1014.6 OF THE 2020 FBC-BUILDING CODE. |
| | |
| | 8) SHEET A-201 AT THE BOTTOM LEFT OF SHEET PLEASE |
| | PROVIDE EITHER A DETAIL OR CUT SECTION FOR THE INFILL |
| | OF PROPOSED FLOOR SLAB, SOIL TREATMENT PER 1816.1.4 AND |
| | DOWELING/ REINFORCEMENT OF SLAB. MISSING DETAIL. |
| | 107.2.1. 2020 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION 107.2.1. |
| | CONSTRUCTION DOCUMENTS SHALL BE SUFFICIENT CLARITY TO |
| | INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 9A) SHEET A104 ROOF PLAN, NOR M103 OR M104 SHOW ACCESS |
| | TO THE ROOF FOR ROOF TOP AIR HANDLERS. 2020 FBC-M 306.5 |
| | EQUIPMENT AND APPLIANCES ON ROOFS OR ELEVATED |
| | STRUCTURES. |
| | 2020 FBC-M 306.5 EQUIPMENT AND APPLIANCES ON ROOFS OR |
| | ELEVATED STRUCTURES. WHERE EQUIPMENT REQUIRING ACCESS |
| | OR APPLIANCES ARE LOCATED ON AN ELEVATED STRUCTURE OR |
| | THE ROOF OF A BUILDING SUCH THAT PERSONNEL WILL HAVE TO |
| | CLIMB HIGHER THAN 16 FEET ABOVE GRADE TO ACCESS SUCH |
| | EQUIPMENT OR APPLIANCES, AN INTERIOR OR EXTERIOR MEANS |
| | OF ACCESS SHALL BE PROVIDED. SUCH ACCESS SHALL NOT |
| | REQUIRE CLIMBING OVER OBSTRUCTIONS GREATER THAN 30 |
| | INCHES IN HEIGHT OR WALKING ON ROOFS HAVING A SLOPE |
| | GREATER THAN 4 UNITS VERTICAL IN 12 UNITS HORIZONTAL |
| | (33-PERCENT SLOPE). SUCH ACCESS SHALL NOT REQUIRE THE |
| | USE OF PORTABLE LADDERS. WHERE ACCESS INVOLVES CLIMBING |
| | OVER PARAPET WALLS, THE HEIGHT SHALL BE MEASURED TO THE |
| | TOP OF THE PARAPET WALL. |
| | |
| | 9B) ROOF TOP HATCHES/ ROOF ACCESS/ 2020 FBC-B |
| | 1011.12.2. IN BUILDINGS THAT DO NOT HAVE AN OCCUPIED |
| | ROOF SHALL BE PERMITTED TO BE A ROOF HATCH OR TRAP DOOR |
| | NOT LESS THAN 16 SQUARE FEET IN AREA AND HAVING A |
| | MINIMUM DIMENSION OF 2 FEET. |
| | OR |
| | 9B) 2020 FBC-B 1011.16 LADDERS. PERMANENT LADDERS SHALL |
| | NOT SERVE AS A PART OF THE MEANS OF EGRESS FROM |
| | OCCUPIED SPACES WITHIN A BUILDING. PERMANENT LADDERS |
| | SHALL BE PERMITTED TO PROVIDE ACCESS TO THE FOLLOWING |
| | AREAS: |
| | 1.SPACES FREQUENTED ONLY BY PERSONNEL FOR MAINTENANCE, |
| | REPAIR OR MONITORING OF EQUIPMENT. |
| | 5.NONOCCUPIED ROOFS THAT ARE NOT REQUIRED TO HAVE |
| | STAIRWAY ACCESS IN ACCORDANCE WITH SECTION |
| | 1011.12.1. |
| | 6.LADDERS SHALL BE CONSTRUCTED IN ACCORDANCE WITH |
| | SECTION 306.5 OF THE FLORIDA BUILDING CODE, |
| | MECHANICAL. |
| | |
| | 10) SHEET A201: |
| | 10A) THE FLOOR PLAN SHOWS THE HIGH-LOW DRINKING |
| | FOUNTAINS BUT NOT COMPLIANCE WITH: |
| | |
| | 10A)(1) PROTRUDING OBJECTS 307.2 PROTRUSION LIMITS |
| | 307.2. OBJECTS WITH LEADING EDGES MORE THAN 27 INCHES |
| | AND NOT MORE THAN 80 INCHES ABOVE THE FLOOR SHALL NOT |
| | PROTRUDE MORE THAN 4 INCHES HORIZONTALLY INTO THE |
| | CIRCULATION PATH. |
| | |
| | 10A)(2) 602.2 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE |
| | COMPLYING WITH 305, POSITIONED FOR A FORWARD APPROACH, |
| | AND KNEE AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE |
| | PROVIDED. |
| | |
| | |
| | 10A)(3) SPOUT OUTLETS/ DRINKING FOUNTAINS. 2017 ACCESS. |
| | CODE. SPOUT OUTLETS SHALL COMPLY WITH: |
| | 602.4 SPOUT HEIGHT. 36 INCHES MAXIMUM ABOVE THE FINISH |
| | FLOOR OR GROUND FOR WHEELCHAIR BOUND INDIVIDUALS. |
| | 602.7 SPOUT HEIGHT FOR THE STANDING PERSONS SHALL BE |
| | BETWEEN 38 TO 43 INCHES ABOVE FINISH FLOOR. |
| | |
| | 10B) JANITORS CLOSET # 120 WITH MOP SINK FINISH |
| | SCHEDULE FOR WALLS INDICATES WALL PAINT FINISH A601. |
| | 2020 FBC-B 1210.2.2. WALLS & PARTITIONS. THIS COMMENT |
| | IS A RESULT OF THE BUILDING OFFICIAL INTERPRETATION ON |
| | 06/2020. IN BATHROOMS, RESTROOMS & SERVICE SINK AREAS |
| | EPOXY PAINT IS NO LONGER CONSIDERED A SMOOTH HARD, |
| | NON-ABSORBENT SURFACE. |
| | |
| | 10C) BATHROOMS 111,121 & 123 ON THE FINISH SCHEDULE |
| | (A601) INDICATE PAINT FINISH. 2020 FBC-B 1210.2.2. |
| | WALLS & PARTITIONS. THIS COMMENT IS A RESULT OF THE |
| | BUILDING OFFICIAL INTERPRETATION ON 06/2020. IN |
| | BATHROOMS, RESTROOMS & SERVICE SINK AREAS EPOXY PAINT |
| | IS NO LONGER CONSIDERED A SMOOTH HARD, NON-ABSORBENT |
| | SURFACE. |
| | |
| | 10D) 2020 FBC-B 2509.2 BASE FOR TILE. MATERIALS USED AS |
| | A BASE FOR WALL TILE IN TUB AND SHOWER AREAS AND WALLS |
| | AND CEILING PANELS IN SHOWER AREAS SHALL BE OF |
| | MATERIALS LISTED IN TABLE 2509.2 AND INSTALLED IN |
| | ACCORDANCE WITH MANUFACTURER???S RECOMMENDATIONS. WATER |
| | RESISTANT GYPSUM (MR BOARD) SHALL NOT BE USED FOR |
| | SHOWER & TUB ENCLOSURES BUT CAN BE USED FOR BACKING |
| | BOARD FOR A BASE FOR TILE IN WATER CLOSET COMPARTMENT |
| | WALLS WHEN INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM |
| | C840 AND THE MANUFACTURE???S RECOMMENDATIONS. |
| | |
| | 10E) 2509.1. WET AREAS. SHOWERS AND PUBLIC TOILET WALLS |
| | SHALL COMPLY WITH 1210.2. |
| | |
| | 11) SHEET A601 ACCESSIBLE DETAILS: |
| | |
| | 11A) DETAILS ARE SHOWN FOR TOILET PARTITIONS BUT LAV |
| | NOT INCLUDED IN THE TOILET STALL, DISCREPANCY FROM THE |
| | FLOOR PLAN A102, NOT SHOWING COMPLIANCE WITH 2020 |
| | FBC-ACCESSIBILITY CODE SECTION 604.3.1 & FIGURE 604.3.1 |
| | CLEARANCE AT WATER CLOSETS. THE 2020 FBC-ACCESSIBILITY |
| | CODE SECTION 604.3.1 & FIGURE 604.3.1 CLEARANCE AT |
| | WATER CLOSETS AND OVERLAP IN SECTION 604.3.2. |
| | |
| | 11B) HEIGHT OF GRAB BARS. GRAB BARS/ RESTROOMS. 2020 |
| | FBC-ACCESSIBILITY CODE SECTION 609.4 POSITION OF GRAB |
| | BARS. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL |
| | POSITION, 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE |
| | THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING |
| | SURFACE, NOT CENTERLINE. |
| | |
| | 11C) URINAL HEIGHT FOR STANDARD, TYPO CAN NOT READ. |
| | 107.2.1. ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 11D) SHEET A102 TOILET ROOM 111 WITH INSWING DOOR DOES |
| | NOT SHOW MANEUVERING CLEARANCES 2020 FBC-ACCESSIBILITY |
| | CODE SECTION 604.3.1 & FIGURE 604.3.1 CLEARANCE AT |
| | WATER CLOSETS. THE 2020 FBC-ACCESSIBILITY CODE SECTION |
| | 604.3.1 & FIGURE 604.3.1 CLEARANCE AT WATER CLOSETS AND |
| | OVERLAP IN SECTION 604.3.2. |
| | |
| | 11E) TOILET ROOM DOORS. 2020 FBC-ACCESSIBILITY CODE |
| | PLEASE REVIEW SECTION 603.2.3. DOORS SHALL NOT SWING |
| | INTO THE CLEAR FLOOR SPACE OR CLEARANCES REQUIRED FOR |
| | ANY FIXTURE. DOORS SHALL BE PERMITTED TO SWING INTO THE |
| | REQUIRED TURNING SPACE. PLEASE SEE EXCEPTION 2. WHERE |
| | TOILET ROOMS ARE FOR INDIVIDUAL USE AND A CLEAR FLOORS |
| | SPACE COMPLYING WITH 305.3 IS PROVIDED WITHIN THE ROOM |
| | BEYOND THE ARC OF THE DOOR SWING. WHAT IS MISSING IS |
| | THE REQUIRED 30X48 INCH CLEAR FLOOR SPACE BEYOND THE |
| | ARC OF THE DOOR. USUALLY AT A 45% ANGLE TO THE DOOR |
| | ENTRANCE. |
| | |
| | 12) SHEET A102 ROOM 116 THE BREAK ROOM THERE ARE NO |
| | DETAIL IF THERE IS COUNTERS AND CHAIRS. |
| | |
| | 12)(A) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR |
| | SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD |
| | APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE |
| | COMPLYING WITH 306 SHALL BE PROVIDED. |
| | |
| | 12)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND |
| | WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | 13) SHEET A101 SHOWS THE LOBBY WITH RECEPTION DESK BUT |
| | NO DETAIL SHOWING COMPLIANCE WITH THE 2020 FL |
| | ACCESSIBILITY CODE SECTIONS: CHECK WRITING SURFACES. |
| | 2020 ACCESS. CODE 904.3.3 CHECK WRITING SURFACES. WHERE |
| | PROVIDED, CHECK WRITING SURFACES SHALL COMPLY WITH |
| | 902.3HEIGHT. THE TOPS OF WORK SURFACES SHALL BE 28 |
| | INCHES MINIMUM AND 34 INCHES MAXIMUM ABOVE THE FINISH |
| | FLOOR OR GROUND. |
| | |
| | 14) SHEETS A101 & A102 ARE MISSING COMPLIANCE WITH THE |
| | 2020 FBC-ACCESSIBILITY CODE SECTION 1004. 1. CLEAR |
| | FLOOR SPACE FOR EXERCISE MACHINES AND EQUIPMENT. |
| | |
| | 15) A TRANSMITTAL LETTER / NARRATIVE LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT |
| | REMARKS MAYBE MADE IN THE NEXT REVIEW CYCLE. |
| | |
| | |
| | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| | PART-TIME/ SEMI-RETIRED. |
| | |
| | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| | BACK INTO THE OFFICE CALL |
| | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| | THANK YOU. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |