| Plan Review Notes For Permit 23011306 |
| Permit Number |
23011306 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2023-04-05 12:20:13 | PLAN DENIED | | | REFER TO SECTION C403.2.4.3 SHUTOFF DAMPERS. | | | 2020 FLORIDA ENERGY CODE. NEED AUTOMATIC | | | DAMPERS ON FRESH AIR DUCT. | | | | | | REFER TO SECTIOIN 607.5.5 SHAFT ENCLOSURES 2020FBC (M) | | | NEED FIRE SMOKE DAMPER AT SHAFT. | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 | | | |
|