| 2023-01-30 08:17:32 | |
| | 1ST REVIEW FBC-2020 RES. GAS |
| | PERMIT- 23011265 |
| | 1/30/2023 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET A1.0: SUBMIT A GAS PIPING RISER FOR |
| | INSTALLATION OF THE NEW TANKLESS WATER HEATER- SEC. |
| | 107.3.5.3 WPB. THE RISER SHALL SHOW THE NEW GAS PIPING |
| | TO THE WATER HEATER AND ALL EXISTING GAS PIPING AND |
| | APPLIANCES AT THE RESIDENCE- SECTION G2412.3 & G2412.4 |
| | FBC RES. REFER TO FBC RES. CHAPTER 24 FUEL GAS AND |
| | PROVIDE THE FOLLOWING INFORMATION ON THE DRAWING- |
| | A) TYPE OF GAS- NATURAL OR LP. |
| | B) DELIVERY PRESSURE AT THE METER. |
| | C) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS. |
| | D) TYPES AND SIZES OF PIPING. |
| | E) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER |
| | TO THE MOST REMOTE APPLIANCE OUTLET. |
| | F) BRANCH AND CUT PIPE LENGTH MEASUREMENTS. |
| | G) LOCATIONS OF REGULATORS, SHUTOFF VALVES. |
| | H) OUTLET PRESSURES AT REGULATORS. |
| | I) LOCATIONS AND TYPES OF PIPE SLEEVES. |
| | K) PIPE SIZING TABLES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |