| Plan Review Notes For Permit 23011257 |
| Permit Number |
23011257 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-02-07 10:35:33 | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW | | | | | | 1. PROVIDE INFORMATION ABOUT "TH-1" PANEL (FEEDERS AND | | | PROTECTION POWERING THIS PANEL). NEC 220, 240, TABLE | | | 310.15(B)(16) | | | | | | 2. THE "TH-1" PANEL SCHEDULE INFORMATION IS BLURRY | | | (DIFFICULT TO READ AND UNDERSTAND). RE-SUBMIT "TH-1" | | | PANEL SCHDULE. FBC 107.2 | | | | | | END OF COMMENTS | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | RUBEN PEREZ PERDOMO, P.E. | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6738 | | | |
|