| | 1ST REVIEW: FBC 2020 7TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| | CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. |
| | |
| | 1. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL5259-R37 |
| | COVERS MULTIPLE ATTACHMENT LIMITATIONS. SELECTED |
| | ATTACHMENT LIMITATION SYSTEM USED FROM 5.8.3.2 |
| | MECHANICALLY-ATTACHED BASE SHEET TABLE 4B ALLOWABLE |
| | DESIGN PRESSURES, 2-PLY UNDERLAYMENT SYSTEMS IN TILE |
| | ROOF APPLICATIONS SYSTEM NO. UDL-13 DO NOT MEET OR |
| | EXCEED THE MINIMUM DESIGN PRESSURE REQUIREMENTS FOR A |
| | HIP ROOF; 5/12 ROOF SLOPE; MEAN ROOF HEIGHT 12 FT. |
| | MINIMUM DESIGN PRESSURE REQUIREMENT OF -70 AS PER |
| | CHAPTER 3 OF THE 2020 FBC RESIDENTIAL. SELECT SYSTEM |
| | THAT MEETS OR EXCEEDS THIS REQUIREMENT. ALL APPLICABLE |
| | DETAILS AND ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON |
| | THE PRODUCT APPROVAL DRAWINGS. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |