| 2023-02-16 12:26:03 | 1ST PLUMBING REVIEW |
| | |
| | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| | |
| | 1. 2020 FRC P3107.1 - THE COMMON VENT SERVING THE LAV, |
| | BATHTUB, WASHER, AND LAUNDRY TUB IS NON-COMPLIANT. A |
| | COMMON VENT CAN ONLY SERVE FIXTURES ON THE SAME FLOOR. |
| | |
| | 2. 2020 FRC P3201.7 - THE TRAP SIZE SHOWN FOR THE |
| | WASING MACHINE IS 1 1/2" AND THE MINIMUM IS 2". |
| | |
| | 3. 2020 FRC P3107.1 - THE SHOWER UPSTAIRS CANNOT DRAIN |
| | DOWN ONTO THE LAVATORY AS EITHER A COMMON VENT. THEY |
| | WOULD HAVE TO BE ON THE SAME FLOOR LEVEL. |
| | |
| | 4. 2020 FRC P3108.2.1 - THE DOWNSTAIRS SHOWER AND WATER |
| | CLOSET ARE NOT VENTED TO CODE. ONLY ONE TRAPPED FIXTURE |
| | IS ALLOWED TO BE UPSTREAM OF THE VENTED FIXTURE'S |
| | CONNECTION TO THE WET VENT. YOU CURRENTLY HAVE 2 |
| | UPSTREAM (OF THE LAV THAT IS NOT VENTED CORRECTLY DUE |
| | TO THE SHOWER UPSTAIRS). |
| | |
| | 5. THE KITCHEN SINK IS INCORRECTLY LABELED AS A "LAV". |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | |
| | RYAN W. BROWN |
| | CHIEF PLUMBING INSPECTOR |
| | OFFICE: 561-805-6692 |
| | CELL: 561-517-4293 |
| | EMAIL: [email protected] |
| | |
| | |
| | V7 FPC - 2020 FLORIDA PLUMBING CODE |
| | V7 FGC - 2020 FLORIDA FUEL GAS |
| | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE |
| | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE |
| | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE |
| | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION |
| | 2021 F.S. - 2021 FLORIDA STATUTES |
| | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE |
| | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE |
| | FBC CHAPTER 1 |
| | |