| 2023-03-02 09:00:45 | ELECTRIC REVIEW FAILED |
| | |
| | 1) IT APPEARS ELECTRICAL DRAWINGS ARE INCOMPLETE. NEW |
| | FLOOR PLAN DETAILS A KITCHEN, DEN, DINING ROOM, FRONT |
| | PORCH AND SECOND FLOOR BATHROOM, AND BEDROOMS ARE TO BE |
| | RENOVATED. ELECTRIC PLANS DO NOT DETAIL ALL WIRING THAT |
| | WILL BE MODIFIED OR ADDED. IN ADDITION, NOTES STATE |
| | THAT ALL EXTERIOR WALLS ARE TO BE INSULATED AND |
| | CONDUITS ARE TO BE INSTALLED IN THESE WALLS. PLEASE |
| | PROVIDE A COMPLETE ELECTRICAL PLAN AS APPLICABLE. |
| | |
| | FBC 107.2, CONSTRUCTION DOCUMENTS SHALL BE OF |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL |
| | |
| | 2) PLEASE PROVIDE AN ELECTRICAL RISER DETAILING ALL |
| | EQUIPMENT, CONDUIT, CONDUCTORS, GROUNDING ELECTRODE |
| | SYSTEM, AND OVERCURRENT PROTECTION. |
| | |
| | NEC 215.5 DIAGRAMS OF FEEDERS. IF REQUIRED BY THE |
| | AUTHORITY HAVING JURISDICTION, A DIAGRAM SHOWING FEEDER |
| | DETAILS SHALL BE PROVIDED PRIOR TO THE INSTALLATION OF |
| | THE FEEDERS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | MICHAEL PETERSON |
| | ELECTRICAL PLANS EXAMINER |
| | [email protected] |
| | 561-805-6746 |
| | |