| Notes |
| Date |
Text |
| 2023-02-22 15:22:18 | GENERATOR | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) PLEASE PROVIDE THE CONCRETE SLAB AND GENERATOR TIE | | | DOWN DETAILS - FBC R301.2.1 | | | | | | 2) PLEASE SHOW THAT THE GENERATOR EXHAUST IS 10 FEET | | | FROM DWELLING WINDOW AND DOOR OPENINGS - FBC R303.5.1 |
|