| 2023-06-21 11:33:07 | THE PREVIOUS FIRE COMMENTS WERE NOT ADDRESSED AND ARE |
| | RESUBMITTED BELOW. |
| | |
| | PLEASE PROVIDE A OFFICIAL RESPONSE TO EACH COMMENT. |
| | |
| | |
| | ******************************************************* |
| | ********************************************** |
| | |
| | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) THERE IS AN INDICATION OF "DOOR FRAME" ON THE |
| | APPLICATION; HOWEVER, THERE IS NO INDICATION OF SCOPE |
| | OF WORK. |
| | |
| | PER NFPA 1 |
| | |
| | 1.7.12 PLANS AND SPECIFICATIONS. |
| | |
| | 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| | PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| | APPLICABLE CODES AND STANDARDS |
| | |
| | FOR THE OFFICIAL RECORD, PLEASE PROVIDE A DETAILED |
| | SCOPE OF WORK. |
| | |
| | |
| | 1A) PER SCOPE OF WORK COMMENT ABOVE, PLEASE PROVIDE ALL |
| | APPLICABLE DOOR SCHEULE INCLUDING, BUT NOT LIMITED TO, |
| | DOOR SPECS, REQUIRED FIRE RATINGS, LOCK/LATCHING |
| | HARDWARE, ETC. |
| | |
| | PER NFPA 1 |
| | |
| | 1.7.12 PLANS AND SPECIFICATIONS. |
| | |
| | 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| | PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| | APPLICABLE CODES AND STANDARDS |
| | |
| | SHOULD THE EXISTING DOOR AND HARDWARE IS EXXISTING AND |
| | WILL BE REPLACED WITHIN THE NEW DOOR FRAME, PLAESE |
| | INDICATE SUCH. |
| | |
| | OTHERWISE PLEASE PROVIDE THE APPLICABLE DOOR SCHEDULE |
| | DETAILS. |
| | |
| | |
| | |
| | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |