| Plan Review Notes For Permit 23011174 |
| Permit Number |
23011174 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-03-06 08:46:24 | PLEASE SUBMIT ENGINEERED DESIGN PRESSURESD. MRH APPEARS | | | TO EXCEED 60'. | | 2023-03-06 08:39:22 | 1. PLEASE SUBMIT A COMPLETE SCOPE OF WORK. PLEASE | | | INCLUDE ENGINEERED DRAWINGS IF THIS IS A DOOR OPENING | | | RENOVATION/MODIFICATION,SITE BUILT AND DESIGNED, OR | | | PLEASE SUBMIT FBC/NOA IF THIS IS SIMPLY A DOOR CHANGE | | | OUT, LIKE FOR LIKE. 2. PLEASE PROVIDE A FLASHING | | | DETAIL, OR ADD A NOTE TO THE PLAN, DEMONSTRATING | | | COMPLIANCE WITH FBC R 703.4 OR FBC B 1405.4 3. PLEASE | | | PROVIDE A FLOOR PLAN/DRAWING/SKETCH SHOWING ROOM | | | DESIGNATIONS, LOCATION OF ALL WINDOWS/DOORS, SIZES, | | | EXISTING WINDOW/DOOR TYPES, AND PROPOSED WINDOW/DOOR | | | TYPES. FBC EB702.5. |
|