| 2023-02-02 10:31:49 | 1ST REVIEW FMC |
| | PERMIT: 23011162 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M-600: IN THE VENTILATION RATES SCHEDULE THE |
| | ROOMS ARE IDENTIFIED AS LOBBY ON BOTH FLOORS. TABLE |
| | 403.3.1.1 INDICATES LOBBIES TO BE CALCULATED WITH AN |
| | OCCUPANCY DENSITY OF 150 WITH A PERSON CFM OF 7.5 AND |
| | THE BREATHING ZONE CFM/SQ FT. OF 0.06. WITH USING |
| | LOBBIES FROM TABLE 403.3.1.1 THE OUTDOOR AIR |
| | CALCULATION FOR BOTH LOBBIES ARE LOW. PLEASE PROVIDE |
| | THE CORRECTED VENTILATION RATES FOR THESE SPACES. FMC |
| | 403.3.1.1 AND TABLE 403.3.1.1 |
| | |
| | 2) THESE DRAWINGS INDICATE THAT THIS IS ONLY THE |
| | BUILDING SHELL. SHEET T.100 INDICATES THIS DESIGN OF |
| | THIS BUILDING IS FOR WORST CASE SCENARIO WHICH IS |
| | ASSEMBLY A-2 BUT SHEET M-600 IN THE BASIS OF DESIGN FOR |
| | FUTURE TENANTS DOES NOT REFLECT THE OUTDOOR AIR OR |
| | EXHAUST REQUIREMENTS FOR THE WORST CASE SCENARIO. |
| | EITHER REMOVE ALL COMMENTS AND TABLES FOR THE FUTURE |
| | USE OR PROVIDE THE CORRECTED SCHEDULES REQUIRED FOR THE |
| | ASSEMBLY A-2 THAT IS STATED ON SHEET T.100. FMC |
| | 403.3.1.1; TABLE 403.3.1.1 AND FBC 107.3.5 |
| | |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |