Plan Review Notes
Plan Review Notes For Permit 23011137
Permit Number 23011137
Review Stop E
Sequence Number 2
Notes
Date Text
2023-04-18 16:19:16FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 ELECTRICAL REVIEW STATUS: PASS, SEE COMMENTS BELOW
  
 1. NEW EXTERIOR CABANA PANEL 100 AMP NEEDS TO FOLLOW
 NEC 250.32 BUILDINGS SUPPLIED BY A FEEDER.
 NOTE: A BUILDING SUPPLIED BY A FEEDER MUST HAVE A
 GROUNDING ELECTRODE SYSTEM AND A GROUNDING ELECTRODE
 CONDUCTOR INSTALLED.
  
 2. PROVIDE DISCONNECTING MEANS FOR A/C EQUIPMENT
 (CONDENSER UNIT) PER NEC 440.14 OR IRC E4101.5
 DISCONNECTING MEANS IS REQUIRED TO BE LOCATED WITHIN
 SIGHT FROM AND READILY ACCESSIBLE FROM THE
 AIR-CONDITIONING EQUIPMENT.
  
 END OF COMMENTS
  