| Notes |
| Date |
Text |
| 2023-04-18 16:19:16 | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | ELECTRICAL REVIEW STATUS: PASS, SEE COMMENTS BELOW | | | | | | 1. NEW EXTERIOR CABANA PANEL 100 AMP NEEDS TO FOLLOW | | | NEC 250.32 BUILDINGS SUPPLIED BY A FEEDER. | | | NOTE: A BUILDING SUPPLIED BY A FEEDER MUST HAVE A | | | GROUNDING ELECTRODE SYSTEM AND A GROUNDING ELECTRODE | | | CONDUCTOR INSTALLED. | | | | | | 2. PROVIDE DISCONNECTING MEANS FOR A/C EQUIPMENT | | | (CONDENSER UNIT) PER NEC 440.14 OR IRC E4101.5 | | | DISCONNECTING MEANS IS REQUIRED TO BE LOCATED WITHIN | | | SIGHT FROM AND READILY ACCESSIBLE FROM THE | | | AIR-CONDITIONING EQUIPMENT. | | | | | | END OF COMMENTS | | | | | | RUBEN PEREZ PERDOMO, P.E. | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6738 | | | [email protected] | | | |
|