Plan Review Notes For Permit 23011137
Permit Number 23011137
Review Stop E
Sequence Number 1
Notes
Date Text
2023-02-03 14:52:15FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW
  
 1. REVIEW GROUNDED CONDUCTOR ON NEW 200A METER MAIN
 COMBO W/ MAIN BREAKER TO BE IN ACCORDANCE WITH NEC
 TABLE 250.102(C)(1).
 2. PROVIDE INFORMATION OF THE EGC FOR THE NEW EXTERIOR
 W.P. CABANA SUBPANEL 100A. NEC 250.122
  
 END OF COMMENTS
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  