| 2023-05-24 16:19:13 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2020 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 23011136 |
| | ADD: 1013 N RAILROAD AVE. |
| | CONT: HEDRICK BROTHERS CONSTRUCTION |
| | TEL: 561-308-2954 |
| | E-MAIL: [email protected] |
| | |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: WED. 02/22/23 |
| | ACTION: PASSED/ BUILDING PROVISOS |
| | |
| | 1) BUILDING PROVISO: SHEET S.002 HAS HEADING DEALING |
| | WITH WELDING & STRUCTURAL STEEL FOR THE PROJECT. WELDED |
| | OR BOLTED CONNECTIONS. THIS BUILDING CONTAINS EITHER |
| | BOLTED AND OR WELDED CONNECTIONS. THE CONTRACTOR IS |
| | REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS & |
| | WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN |
| | ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF |
| | INSPECTION FOR FIELD WIELDING, ON THE JOB-SITE |
| | WIELDING. THIRD PARTY CERTIFICATION WILL BE REQUIRED. |
| | THE OWNER MAY JUST HIRE A 3RD PARTY ENGINEERING FIRM TO |
| | COMPLETE AND APPROVE THE FORMER INSPECTIONS. REPORTS |
| | SUBMITTED TO BUILDING INSPECTOR AT TIME OF FRAMING |
| | INSPECTION. |
| | 2020 FBC-B 2204.1 WELDING |
| | 1. WELD PROCEDURES SPECIFICATIONS |
| | 2. QUALIFICATIONS OF WELDING PERSONAL |
| | 2017 FBC-B 2204.2 BOLTING. |
| | IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED, |
| | PLEASE CONTACT THE CHIEF BUILDING INSPECTOR RICHARD |
| | BRUNELLE AT 561-805-6670. |
| | |
| | 2) BUILDING PROVISO/ DEFERRED SUBMITTALS/ COMPONENTS & |
| | CLADDING. |
| | COMPONENTS & CLADDING. PLEASE SUBMIT THE COMPONENTS AND |
| | CLADDING PRODUCT APPROVALS. 2020 FBC-B 1609.1.2 |
| | PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS & |
| | CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, |
| | ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/ |
| | 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS, MULLIONS & ROOF HATCHES. |
| | (B) WINDOWS & MULLIONS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES, LIGHTWEIGHT |
| | CONCRETE INSULATION, ROOF TOP VENTILATORS |
| | (G) PRE-ENGINEERED A/C STANDS |
| | |
| | 3) BUILDING PROVISO: W. P. B. 107.3.4. PRODUCT |
| | APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY |
| | FLORIDA ADMINISTRATIVE CODE RULE 61G20 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING (SHOP DRAWING STAMP OF |
| | APPROVAL) BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC. |
| | |
| | 4) BUILDING PROVISO: DELEGATED ENGINEERING. |
| | 61G15-30.003 ENGINEERING DOCUMENT CLASSIFICATION. FL |
| | 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL FORWARD |
| | THE DELEGATED ENGINEERING DOCUMENTS TO THE ENGINEER OF |
| | RECORD FOR REVIEW. |
| | |
| | 5) BUILDING PROVISO: IDENTIFY GLAZING/ MULLIONS. PLEASE |
| | IDENTIFY IN THE PRODUCT APPROVAL BEFORE SUBMITTING TO |
| | DESIGNER OF RECORD AND BEFORE SUBMISSION TO THE |
| | BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, |
| | PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, SILL |
| | HEIGTH, TYPE OF GLAZING, MULLION SIZE, LENGTH IF |
| | UNREINFORCED OR REINFORCED INFORMATION IF REQUIRED, |
| | ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING |
| | SIZE. 2020 FBC-B 1405.13.1 INSTALLATION. WINDOWS AND |
| | DOORS SHALL BE INSTALLED IN ACCORDANCE WITH APPROVED |
| | MANUFACTURER???S INSTRUCTIONS. FASTENER SIZE AND |
| | SPACING SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND |
| | SHALL BE CALCULATED BASED ON MAXIMUM LOADS AND SPACING |
| | USED IN THE TESTS. |
| | |
| | 6) BUILDING PROVISO: 2020 FBC-BUILDING CODE SECTION |
| | 1405.4. FLASHINGS SHALL BE INSTALLED AT THE PERIMETERS |
| | OF EXTERIOR DOORS & WINDOW ASSEMBLIES. WHEN |
| | SELF-ADHERED MEMBRANES ARE USED AS FLASHINGS IN WALL |
| | ASSEMBLIES, THOSE SELF-ADHERED FLASHINGS SHALL COMPLY |
| | WITH AAMA-711. |
| | |
| | 7) BUILDING PROVISO: ROOFING: FOR ALL ROOFING PRODUCTS |
| | PLEASE IDENTIFY ALL ROOFING SUB-SYSTEMS AND THEIR |
| | ASSOCIATED PRESSURES FOR ROOF ZONE # 1. REVIEW THE |
| | PRODUCT APPROVAL LIMITATIONS, IF ENHANCED FASTENING IS |
| | ALLOWED FOR ROOF ZONES 2 & 3. FASTENER DENSITIES SHALL |
| | BE INCREASED FOR BOTH INSULATION & THE BASE SHEET AS |
| | CALCULATED IN COMPLIANCE WITH ROOFING APPLICATION |
| | STANDARDS RAS 117. CALCULATION PREPARED, SIGNED AND |
| | SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR |
| | REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS & |
| | CLADDING. |
| | |