| 2023-02-03 07:02:14 | 1ST REVIEW FMC |
| | PERMIT: 23011136 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M-600: SUBMIT ONLY THE INFORMATION THAT IS |
| | RELEVANT TO TAKING THIS CHANGE OF OCCUPANCY BACK TO A |
| | SHELL. THERE IS NO LOBBY SHOWN ON THESE SUBMITTED |
| | DRAWINGS. THERE IS NO 2ND FLOOR, REMOVE THIS FROM THE |
| | BASIS OF DESIGN ON SHEET M-600. THE SHEET T.100 |
| | INDICATES THIS SPACE IS DESIGNED FOR WORSE CASE WHICH |
| | IS AN ASSEMBLY A-2. THE INFORMATION ON SHEET M-600 |
| | WOULD NOT WORK, THE SQUARE FOOTAGE SHOWN ON T.100 FOR |
| | THE KITCHEN AND THE DINING ROOM WOULD REQUIRE A TOTAL |
| | OF 4,522 CFM???S OF OUTDOOR AIR AND THE KITCHEN WOULD |
| | REQUIRE 1,881 CFM???S OF EXHAUST. THE BASIS OF DESIGN |
| | ON M.600 DOES NOT SHOW THIS SO THE ROOF GRAVITY |
| | VENTILATOR SCHEDULE WOULD NOT WORK. SHEET M-500 SHOULD |
| | BE REMOVED AS THERE IS NO MECHANICAL SYSTEM SHOWN FOR |
| | THIS SHELL. FMC 403.3.1.1 AND TABLE 403.3.1.1; FBC |
| | 107.3.5 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |