| 2023-02-02 16:43:29 | 1ST REVIEW FMC |
| | PERMIT: 23011135 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M-600: SUBMIT ONLY THE INFORMATION THAT IS |
| | RELEVANT TO TAKING THIS CHANGE OF OCCUPANCY BACK TO A |
| | SHELL. THERE IS NO LOBBY SHOWN ON THESE SUBMITTED |
| | DRAWINGS. THERE IS NO 2ND FLOOR SHOWN FOR THIS PROJECT. |
| | THE T.100 INDICATES THIS SPACE IS DESIGNED FOR WORSE |
| | CASE WHICH IS AN ASSEMBLY A-2. THE INFORMATION ON SHEET |
| | M-600 WOULD NOT WORK, THE SQUARE FOOTAGE SHOWN ON T.100 |
| | FOR THE KITCHEN AND THE DINING ROOM WOULD REQUIRE A |
| | TOTAL OF 2,863 CFM???S OF OUTDOOR AIR AND THE KITCHEN |
| | WOULD REQUIRE 1,183 CFM???S OF EXHAUST. THE BASIS OF |
| | DESIGN ON M.600 DOES NOT SHOW THIS SO THE ROOF GRAVITY |
| | VENTILATOR SCHEDULE WOULD NOT WORK. FMC 403.3.1.1 AND |
| | TABLE 403.3.1.1; FBC 107.3.5 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |