| 2023-02-22 13:03:56 | SFR REMODEL |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | |
| | 1) FOR THE EXISTING GARAGE THE DRAWINGS SAY TO RAISE |
| | THE FLOOR - PLEASE PROVIDE THE DETAILS TO RAISE THE |
| | FLOOR - FBC WPB 701.2.1 |
| | |
| | 2) PLEASE PROVIDE DETAILS FOR THE ATTACHMENT OF THE |
| | GARAGE DOOR TO THE EXTERIOR WALL - FBC R703.1.2 |
| | |
| | 3) FOR THE GARAGE DOOR WALL FILL IN - PLEASE SHOW THAT |
| | A WATER RESISTIVE BARRIER IS REQUIRED - R703.1.1 WATER |
| | RESISTANCE. |
| | THE EXTERIOR WALL ENVELOPE SHALL BE DESIGNED AND |
| | CONSTRUCTED IN A MANNER THAT PREVENTS THE ACCUMULATION |
| | OF WATER WITHIN THE WALL ASSEMBLY BY PROVIDING A |
| | WATER-RESISTANT BARRIER BEHIND THE EXTERIOR CLADDING AS |
| | REQUIRED BY SECTION R703.2 AND A MEANS OF DRAINING TO |
| | THE EXTERIOR WATER THAT PENETRATES THE EXTERIOR |
| | CLADDING. R703.2 WATER-RESISTIVE BARRIER. |
| | ONE LAYER OF NO. 15 ASPHALT FELT, FREE FROM HOLES AND |
| | BREAKS, COMPLYING WITH ASTM D226 FOR TYPE 1 FELT OR |
| | OTHER APPROVED WATER-RESISTIVE BARRIER SHALL BE APPLIED |
| | OVER STUDS OR SHEATHING OF ALL EXTERIOR WALLS. NO. 15 |
| | ASPHALT FELT SHALL BE APPLIED HORIZONTALLY, WITH THE |
| | UPPER LAYER LAPPED OVER THE LOWER LAYER NOT LESS THAN 2 |
| | INCHES (51 MM). |
| | |
| | 4) FROM GARAGE TO LIVING SPACE - PLEASE SHOW THE |
| | MINIMUM WALL AND CEILING INSULATION TYPE AND "R" VALUE |
| | PER FBC ENERGY TABLE R402.1.2 OR MATCH THE ENERGY |
| | CALCULATIONS. |