| 2023-05-15 11:09:26 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS | | | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. | | | PERMIT #23011125 | | | 214 LINDA LN | | | | | | 1- REVISE ENGINEER CALCULATIONS SUBMITTED: | | | A) THE NAIL FASTENING SPACING SPECIFIED BY THE ENGINEER | | | DOESN'T MATCH THE NAIL FASTENING SPACING LISTED IN THE | | | NOA 18-0919.12 ON PAGE 55 OF 67 FOR A MAXIMUM DESIGN | | | PRESSURES OF -52.5PSF. REVISE AS REQUIRED TO MATCH. | | | SEC. 107.2.1 CITY AMENDMENTS. | | | | | | B)THE ROOF ZONES DESIGN PRESSURES SPECIFIED BY THE | | | ENGINEER ARE TOO LOW. IT LOOKS LIKE ENGINEER IS USING | | | ASCE-7-10 INSTEAD OF CURRENT ASCE-7-16. REVISE AS | | | REQUIRED. SEC. R301.2.1.1 FBC-RESIDENTIAL. | | | | | | C)ENGINEER TO SPECIFY THE DESIGN PRESSURES FOR ALL 4 | | | NEW ROOF ZONES. | | | SEC. R301.2.1.1 FBC-RESIDENTIAL. | | | | | | D)ENGINEER TO REVISE THE PERIMETER WIDTH DIMENSION AND | | | THE CORNER ZONES DIMENSIONS. SEE ASCE 7-16 AND REVISE | | | AS REQUIRED. | | | SEC. R301.2.1.1 FBC-RESIDENTIAL. | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|