| Date |
Text |
| 2023-04-04 11:39:58 | JONATHAN BROOKS JR. |
| | BUILDING PLANS EXAMINER |
| | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| | PHONE (561) 805-6656 |
| | EMAIL: [email protected] |
| | |
| | 1ST REVIEW: FBC 2020 7TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| | CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. |
| | |
| | 1. PROVIDE THE FOLLOWING INFORMATION FOR MIAMI-DADE NOA |
| | NO.: 18-0919.12 FOR THE PROPOSED FLAT ROOF SYSTEM TO BE |
| | USED CORRESPONDING TO ENGINEERS CALCULATIONS. PAGES #1 |
| | & #2, INSTALLATION INSTRUCTIONS FOR SYSTEM E (3) |
| | PAGE(S) #55 & #56 AND LIMITATIONS PAGE(S) #67. ALL |
| | APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY |
| | IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. |
| | 2. FBC B 107.2.1. REVISE SUBMITTED FASTENER DENSITY |
| | CALCULATIONS PREPARED, SIGNED AND SEALED BY A FLORIDA |
| | REGISTERED PROFESSIONAL ENGINEER; TO CORRECT EXPOSURE |
| | CATEGORY, DESIGN PRESSURES & NAILING PATTERNS. THE |
| | EXPOSURE CATEGORY FOR 214 LINDA LN WEST PALM BEACH, FL |
| | 33405 IS EXPOSURE CATEGORY D. |
| | 3. FBC B 107.2.1 FOR CLARITY PLEASE REVISE ROOF |
| | DIAGRAM/SKETCH AND INCLUDE FLAT ROOF SLOPE(S), MEAN |
| | ROOF HEIGHT(S). FLAT/LOW SLOPE ROOFS MUST SHOW POSITIVE |
| | DRAINAGE. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | |