| 2023-03-07 06:37:38 | 2ND PLUMBING REVIEW |
| | |
| | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| | |
| | 1. COMMENT NOT ADDRESSED - THE KITCHEN SINK IS NOT A |
| | BATHROOM GROUP FIXTURE. ONLY BATHROOM GROUP FIXTURES |
| | ARE ALLOWED TO BE INCLUDED WITHIN THE WET VENT FOR THE |
| | BATHROOM. THE KITCHEN SINK MUST DISCHARGE DOWNSTREAM OF |
| | THE LAST BATHROOM GROUP FIXTURE BEING WET VENTED. |
| | POOL HOUSE DIAGRAM - 2020 FRC P3108.1 - THE KITCHEN |
| | SINK CANNOT BE THE VENTED FIXTURE THAT CREATES THE WET |
| | VENT FOR THE BATHROOM GROUP FIXTURES. THE KITCHEN SINK |
| | WOULD NEED TO DISCHARGE DOWNSTREAM OF THE WET VENT |
| | SYSTEM IF A WET VENT IS USED. |
| | |
| | 2. ADDITIONAL COMMENT - ADDTION WASTE DIAGRAM - 2020 |
| | FRC P3108.2.1 - THE TUB AND SHOWER ARE BOTH UPSTREAM OF |
| | THE LAVATORY CONNECTION. ONLY ONE TRAPPED FIXTURE IS |
| | ALLOWED TO BE UPSTREAM OF THE VENTED FIXTURE'S |
| | CONNECTION TO THE HORIZONTAL BRANCH DRAIN BEING WET |
| | VENTED. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | |
| | RYAN W. BROWN |
| | CHIEF PLUMBING INSPECTOR |
| | OFFICE: 561-805-6692 |
| | CELL: 561-517-4293 |
| | EMAIL: [email protected] |
| | |
| | |
| | V7 FPC - 2020 FLORIDA PLUMBING CODE |
| | V7 FGC - 2020 FLORIDA FUEL GAS |
| | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE |
| | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE |
| | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE |
| | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION |
| | 2021 F.S. - 2021 FLORIDA STATUTES |
| | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE |
| | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE |
| | FBC CHAPTER 1 |
| | |