| 2023-02-02 13:30:31 | POOL HOUSE |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | |
| | 1) PLEASE PROVIDE A SOIL REPORT (GEOTECHNICAL REPORT) |
| | FBC 1803.2 |
| | |
| | 2) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE |
| | INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE |
| | PRODUCT APPROVALS FOR THE EXTERIOR SLIDING GLASS DOOR, |
| | EXTERIOR SWING DOOR AND THE ROOFING SYSTEMS - ALL |
| | PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED |
| | APPROVED BY THE BUILDING DESIGNER OF RECORD FBC WPB |
| | 107.3.4 |
| | |
| | 3) PLEASE SHOW THE ROOF SHEATHING TYPE AND THICKNESS - |
| | FBC WPB 107.2.1 |
| | |
| | 4) DRAWING A-1.01 TYPICAL WALL SECTION SHOWS ATTIC |
| | VENTILATION AND SPRAY FOAM INSULATION - SHOULD NOT HAVE |
| | ATTIC VENTILATION WITH FOAM ATTACHED TO THE UNDERSIDE |
| | OF THE ROOF SHEATHING. SEE FOAM INSULATION INSTRUCTIONS |
| | AND PROVIDE THOSE INSTRUCTIONS. (ICC - ES EVALUATION |
| | REPORT) - FBC R316.3 SURFACE BURNING CHARACTERISTICS. |
| | UNLESS OTHERWISE ALLOWED IN SECTION R316.5, FOAM |
| | PLASTIC OR FOAM PLASTIC CORES USED AS A COMPONENT IN |
| | MANUFACTURED ASSEMBLIES USED IN BUILDING CONSTRUCTION |
| | SHALL HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 75 AND |
| | SHALL HAVE A SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450 |
| | WHEN TESTED IN THE MAXIMUM THICKNESS AND DENSITY |
| | INTENDED FOR USE IN ACCORDANCE WITH ASTM E84 OR UL 723. |
| | |
| | 5) PLEASE SHOW THE STORM WATER FLOW AWAY FROM THE |
| | BUILDING AND AWAY FROM THE ADJACENT PROPERTY - FBC WPB |
| | 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED |
| | WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY |
| | A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF |
| | NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE, |
| | DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES |
| | AND THE PROPOSED FINISHED GRADES, DEPICTING THE |
| | PROPOSED LOT DRAINAGE AND, AS APPLICABLE, FLOOD HAZARD |
| | AREAS, FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT |
| | SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND |
| | INCLUDED ON A BOUNDARY LINE SURVEY. (PLEASE PROVIDE CUT |
| | SECTIONS FOR ANY PROPOSED WATER RETAINING SWALES) |