2023-03-02 17:31:48****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC R = FBC RESIDENTIAL
  
 1. FBC R 703.4, FBC B 1405.4, A FLASHING DETAIL OR
 SPECIFICATION IS REQUIRED.
  
 THE PROPOSED DETAILS DO NOT INCLUDE ANY MATERIAL
 STANDARDS. PLEASE REVISE TO INCLUDE.
 THE DETAIL FOR BLOCK APPEARS TO PROPOSE ONLY CAULKING -
 THIS IS NOT FLASHING. FLASHING IS REQUIRED TO DIRECT
 WATER AWAY FROM THE STRUCTURE. AS POINTED OUT BY THE
 BUILDING OFFICIAL, CAULKING COULD ACTUALLY DO THE
 OPPOSITE AND TRAP WATER.
  
  