| Date |
Text |
| 2023-06-01 15:11:15 | 3RD REVIEW FBC-2020 PLUMBING |
| | PERMIT- 23011089 |
| | 6/1/23 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) ARCHITECTURAL AND PLUMBING FLOOR PLANS: 3RD REQUEST |
| | TO IDENTIFY THE BATHROOMS AS MALE, FEMALE OR UNISEX AND |
| | PROVIDE SIGNAGE AS REQUIRED BY SEC. 403.4 FBC P. THE |
| | ARCHITECT'S RESPONSE TO THE PREVIOUS COMMENT #1E CITES |
| | SEC. 403.1.2 WHICH IS A SUB-SECTION OF 403.1- MINIMUM |
| | NUMBER OF FIXTURES. SEC. 403.2 IS THE SECTION THAT |
| | REQUIRES SEPARATE FACILITIES AND THE FOUR EXCEPTIONS |
| | LISTED UNDER 403.2 ARE NOT APPLICABLE TO THE FACILITY. |
| | SEC. 403.2.1 ALLOWS THE USE OF UNISEX WHEN A BUILDING |
| | OR TENANT SPACE REQUIRES A SINGLE TOILET FOR EACH SEX, |
| | HOWEVER THE CALCULATIONS LISTED ON SHEET AC1.01 |
| | INDICATE MULTIPLE TOILETS REQUIRED FOR PATIENTS, STAFF, |
| | AND VISITORS. |
| | |
| | 2) SHEETS P2.00, P2.01, P2.02, & P7.00: BASED ON TABLES |
| | 709.1 & 710.1 IT APPEARS THE ACCUMULATED DFU TOTALS AT |
| | A POINT IN AREA C WILL EXCEED THE CAPACITY OF A 4-INCH |
| | BUILDING DRAIN HOWEVER NO DFU TOTALS HAVE BEEN PROVIDED |
| | AND THE SIZE OF THE EXISTING BUILDING DRAIN IS NOT |
| | SHOWN. |
| | |
| | 3) P2.01, P2.02, P7.00, & FS1.2: BASED ON PREVIOUS |
| | COMMENT #7 PLEASE PROVIDE A KITCHEN PLUMBING FIXTURE |
| | THAT CORRELATES WITH THE FIXTURES SHOWN IN THE KITCHEN. |
| | THIS IS REQUIRED TO DETERMINE WHICH DRAINAGE SHOULD BE |
| | GOING TO SANITARY AND WHICH TO GREASE. |
| | |
| | NEW COMMENT. |
| | |
| | 1) SHEET P2.01: BASED ON SEC. 803.1 FBC P IT APPEARS |
| | THAT A DILUTION OR NEUTRALIZING DEVICE MUST BE PROVIDED |
| | FOR THE DRAINAGE FROM LAB SINK S-5. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |
| | |