| Notes |
| Date |
Text |
| 2023-06-20 10:56:09 | PLAN DENIED | | | 1) PLEASE CLOUD THE CHANGES ON THE SCONED REVIEW | | | SO WE CAN SEE WHAT CHANGES WERE MADE.SECTION 107 FBC. | | | 2) REFER TO SECTION 607.5.4 CORRIDOR/ SMOKE BARRIERS. | | | IF YOU ARE USING SMOKE DAMPERS PLEASE SHOW DAMPERS ON | | | ALL DUCT PENETRATING SMOKE BARRIER PARTITIONS ON THE | | | PLAN. IF YOU ARE NOT | | | USING SMOKE DANPERS SHOW ON THE PLAN WHAT EXCEPTION | | | YOU ARE USING FROM 607.5.4 FBC (M) 2020 | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6766 |
|