Plan Review Notes
Plan Review Notes For Permit 23011089
Permit Number 23011089
Review Stop B
Sequence Number 3
Notes
Date Text
2023-06-01 15:03:22HOSPITAL REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE THE FLORIDA STATE PRODUCT APPROVAL
 FRONT PAGES FOR PRODUCT APPROVALS (FL15850) - (FL8787)
 - (FL4553)
  
 2) THE STRUCTURAL DRAWINGS DO NOT SHOW AS DIGITALLY
 SIGNED IN ADOBE READER - SIGNED AND SEALED DRAWINGS IN
 PROJECTDOX NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED
 TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).
 I CHECK THE ELECTRONIC SIGNATURE FOR THE DRAWINGS
 UPLOADED TO PROJECTDOX BY OPENING THEM IN ???ADOBE
 READER???. THE ???ADOBE READER??? STATES WHETHER THEY
 ARE AN ORIGINAL ELECTRONICALLY SIGNED DOCUMENT. WHEN
 ELECTRONICALLY SIGNED DRAWINGS ARE PRINTED OUT, THEY
 LOSE THEIR ELECTRONIC SIGNATURE. ELECTRONICALLY SIGNED
 DRAWINGS NEED TO BE MOVED AROUND IN THE COMPUTER FROM
 PLACE TO PLACE. FROM THE ARCHITECT???S OR ENGINEER???S
 COMPUTER TO YOUR COMPUTER TO THE CITY???S ELECTRONIC
 PLAN REVIEW (PROJECTDOX). MAYBE YOURS WERE PRINTED OUT
 AT SOME TIME?
  
  
  
  
  