Plan Review Notes
Plan Review Notes For Permit 23011089
Permit Number 23011089
Review Stop P
Sequence Number 2
Notes
Date Text
2023-04-17 13:09:092ND REVIEW FBC-2020 PLUMBING
 PERMIT- 23011089
 4/17/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES.
  
 1) FAILED. AC1.01: THE FIXTURE CALCULATIONS ARE
 INCOMPLETE FOR THE FACILITY. REFER TO TABLE 403.1 FBC P
 AND PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED NUMBER OF FIXTURES. PLEASE NOTE DRINKING
 FOUNTAINS AND SERVICE SINKS ARE REQUIRED FIXTURES FOR
 I-2 OCCUPANCIES. MIXED OCCUPANCY CALCULATIONS SHALL BE
 DONE IN ACCORDANCE WITH SEC. 403.1.1. A COMPLETE REVIEW
 OF THE PROJECT CANNOT BE COMPLETED WITHOUT THE
 CALCULATIONS.
 A) THE REVISED CALCULATIONS AND SCHEDULE LISTING THE
 REQUIRED AND PROVIDED NUMBER OF FIXTURES WAS NOT
 PROVIDED. BASED ON TABLE 403.1 OCCUPANTS LOADS FOR
 STAFF AND VISITORS NEED TO BE BROKEN OUT TO CALCULATE
 THE REQUIRED FIXTURES FOR EACH. THE PLANS APPEAR TO
 SHOW THAT ADEQUATE WATER CLOSETS AND LAVATORIES WILL BE
 PROVIDED FOR PATIENTS, STAFF, AND THE VISITORS HOWEVER
 THE REVIEW CANNOT BE COMPLETED AT THIS TIME.
  
 B) DRINKING FOUNTAINS AND SERVICE SINKS ARE REQUIRED
 FIXTURES AND NO CALCULATIONS AND CORRESPONDING
 LOCATIONS FOR THOSE FIXTURES HAVE BEEN PROVIDED- TABLE
 403.1 FBC P.
  
 C) THE ENGINEER'S RESPONSE TO NOT INSTALL THE DRINKING
 FOUNTAIN'S PER THE HOSPITAL ADMINISTRATION'S REQUEST IS
 NOT ACCEPTED BECAUSE THERE ARE NO EXCEPTIONS IN THE
 PLUMBING CODE FOR HOSPITALS. SECTION 449.3.9.1 FBC B
 REQUIRES PLUMBING SYSTEMS FOR HOSPITALS TO BE DESIGNED
 IN ACCORDANCE WITH THE FBC P. SECTION 410.4 FBC P
 ALLOWS ONLY RESTAURANTS TO SUBTITUTE WATER IN
 CONTAINERS FREE OF CHARGE TO OCCUPANTS. IF THERE IS AN
 EXCEPTION FROM ANOTHER REGULATING AGENCY SUCH AS AHCA
 PLEASE PROVIDE DOCUMENTATION TO VERIFY COMPLIANCE.
  
 D) THERE IS ONE MOP SINK (SB-1) IN THE KITCHEN. CLARIFY
 IF THIS SINK WILL SERVICE ALL THE ROOMS AND AREAS ON
 THE FLOOR.
  
 E) BASED ON SEC. 403.2 SEPARATE FACILITIES SHALL BE
 PROVIDED FOR EACH SEX HOWEVER THE PLANS DO NOT IDENTIFY
 THE RESTROOMS AS MALE OR FEMALE.
  
  
 6) FAILED. PLEASE SUBMIT SANITARY DRAINAGE/VENT AND
 WATER RISER DRAWINGS- SEC. 107.3.5.1.3(13) WPB. PLEASE
 NOTE A COMPLETE REVIEW OF THE PROJECT CANNOT BE
 COMPLETED WITHOUT THE ISOMETRICS. A COMPLETE REVIEW
 CANNOT BE ACCOMPLISHED AT THIS TIME PER ITEMS A & B.
 A) IDENTIFY ALL FIXTURES BASED ON THE SCHEDULE ON SHEET
 P0.02. ONLY THE FIXTURES FROM PART C PLANS ARE
 IDENTIFIED ON THE SANITARY RISER. NO FIXTURES IDENTIFED
 ON THE WATER RISER.
  
 B) LABEL THE GREASE WASTE LINE
  
 7) FAILED. P2.01 & P2.02: PLEASE IDENTIFY THE PLUMBING
 FIXTURES IN THE KITCHEN THAT ARE DRAINING INTO THE
 GREASE WASTE LINE AND INTERCEPTOR- SEC. 1003.3.1 FBC P.
 PLEASE NOTE THAT DRAINAGE FROM HAND SINKS OR ICE BINS
 AND ICE MAKERS SHALL NOT DRAIN INTO THE INTERCEPTOR.
 SHEETS P2.01 & P.2.02 SHOW THE DRAINAGE FROM THE HAND
 SINKS DISCHARGING INTO THE GREASE WASTE LINE WHICH IS
 NOT ALLOWED- SEC. 1003.3.1 FBC P. HANDSINKS ARE NOT
 CONSIDERED TO BE SIGNIFICANT CONTRIBUTORS OF GREASE
 WASTE.
  
 8) FAILED. P0.02, P3.01: INDICATE THE WATER SUPPLY
 TEMPERATURE FOR THE EYE WASH STATION EW-2 WILL BE
 CONTROLLED BY A TEMPERATURE ACTUATED MIXING VALVE
 COMPLYING WITH ASSE 1071- SEC. 411.3 FBC P.
 TEPID WATER AND ASSE 1071 COMPLIANCE NOT NOTED IN THE
 SCHEDULE ON SHEET P0.02.
  
 9) FAILED. P3.00, P3.01, & P3.02: IN ORDER TO MEET
 COMPLIANCE WITH TABLE C404.5.1 FBC ENERGY, THE HW
 RECIRCULATION LINES MUST BE LOCATED AT A POINT WITHIN 2
 FT. OF THE HW SUPPLY PIPES TO THE PUBLIC LAVATORIES.
 THIS INCLUDES ALL BATHROOMS FOR STAFF BUT NOT THE
 PATIENT BATHROOMS.
 REFER TO COMMENT RESPONSE TO 6 AND IDENTIFY THE
 LOCATIONS OF THE PUBLIC LAVATORIES ON THE WATER RISER.
  
  
 12) FAILED. P6.00: SHOW THE LOCATION OF THE THERMAL
 EXPANSION CONTROL DEVICE FOR THE ST-1- SEC. 607.3 FBC
 P. NOT PROVIDED.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved