| Date |
Text |
| 2023-04-17 13:09:09 | 2ND REVIEW FBC-2020 PLUMBING |
| | PERMIT- 23011089 |
| | 4/17/23 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE |
| | 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES. |
| | |
| | 1) FAILED. AC1.01: THE FIXTURE CALCULATIONS ARE |
| | INCOMPLETE FOR THE FACILITY. REFER TO TABLE 403.1 FBC P |
| | AND PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND |
| | PROVIDED NUMBER OF FIXTURES. PLEASE NOTE DRINKING |
| | FOUNTAINS AND SERVICE SINKS ARE REQUIRED FIXTURES FOR |
| | I-2 OCCUPANCIES. MIXED OCCUPANCY CALCULATIONS SHALL BE |
| | DONE IN ACCORDANCE WITH SEC. 403.1.1. A COMPLETE REVIEW |
| | OF THE PROJECT CANNOT BE COMPLETED WITHOUT THE |
| | CALCULATIONS. |
| | A) THE REVISED CALCULATIONS AND SCHEDULE LISTING THE |
| | REQUIRED AND PROVIDED NUMBER OF FIXTURES WAS NOT |
| | PROVIDED. BASED ON TABLE 403.1 OCCUPANTS LOADS FOR |
| | STAFF AND VISITORS NEED TO BE BROKEN OUT TO CALCULATE |
| | THE REQUIRED FIXTURES FOR EACH. THE PLANS APPEAR TO |
| | SHOW THAT ADEQUATE WATER CLOSETS AND LAVATORIES WILL BE |
| | PROVIDED FOR PATIENTS, STAFF, AND THE VISITORS HOWEVER |
| | THE REVIEW CANNOT BE COMPLETED AT THIS TIME. |
| | |
| | B) DRINKING FOUNTAINS AND SERVICE SINKS ARE REQUIRED |
| | FIXTURES AND NO CALCULATIONS AND CORRESPONDING |
| | LOCATIONS FOR THOSE FIXTURES HAVE BEEN PROVIDED- TABLE |
| | 403.1 FBC P. |
| | |
| | C) THE ENGINEER'S RESPONSE TO NOT INSTALL THE DRINKING |
| | FOUNTAIN'S PER THE HOSPITAL ADMINISTRATION'S REQUEST IS |
| | NOT ACCEPTED BECAUSE THERE ARE NO EXCEPTIONS IN THE |
| | PLUMBING CODE FOR HOSPITALS. SECTION 449.3.9.1 FBC B |
| | REQUIRES PLUMBING SYSTEMS FOR HOSPITALS TO BE DESIGNED |
| | IN ACCORDANCE WITH THE FBC P. SECTION 410.4 FBC P |
| | ALLOWS ONLY RESTAURANTS TO SUBTITUTE WATER IN |
| | CONTAINERS FREE OF CHARGE TO OCCUPANTS. IF THERE IS AN |
| | EXCEPTION FROM ANOTHER REGULATING AGENCY SUCH AS AHCA |
| | PLEASE PROVIDE DOCUMENTATION TO VERIFY COMPLIANCE. |
| | |
| | D) THERE IS ONE MOP SINK (SB-1) IN THE KITCHEN. CLARIFY |
| | IF THIS SINK WILL SERVICE ALL THE ROOMS AND AREAS ON |
| | THE FLOOR. |
| | |
| | E) BASED ON SEC. 403.2 SEPARATE FACILITIES SHALL BE |
| | PROVIDED FOR EACH SEX HOWEVER THE PLANS DO NOT IDENTIFY |
| | THE RESTROOMS AS MALE OR FEMALE. |
| | |
| | |
| | 6) FAILED. PLEASE SUBMIT SANITARY DRAINAGE/VENT AND |
| | WATER RISER DRAWINGS- SEC. 107.3.5.1.3(13) WPB. PLEASE |
| | NOTE A COMPLETE REVIEW OF THE PROJECT CANNOT BE |
| | COMPLETED WITHOUT THE ISOMETRICS. A COMPLETE REVIEW |
| | CANNOT BE ACCOMPLISHED AT THIS TIME PER ITEMS A & B. |
| | A) IDENTIFY ALL FIXTURES BASED ON THE SCHEDULE ON SHEET |
| | P0.02. ONLY THE FIXTURES FROM PART C PLANS ARE |
| | IDENTIFIED ON THE SANITARY RISER. NO FIXTURES IDENTIFED |
| | ON THE WATER RISER. |
| | |
| | B) LABEL THE GREASE WASTE LINE |
| | |
| | 7) FAILED. P2.01 & P2.02: PLEASE IDENTIFY THE PLUMBING |
| | FIXTURES IN THE KITCHEN THAT ARE DRAINING INTO THE |
| | GREASE WASTE LINE AND INTERCEPTOR- SEC. 1003.3.1 FBC P. |
| | PLEASE NOTE THAT DRAINAGE FROM HAND SINKS OR ICE BINS |
| | AND ICE MAKERS SHALL NOT DRAIN INTO THE INTERCEPTOR. |
| | SHEETS P2.01 & P.2.02 SHOW THE DRAINAGE FROM THE HAND |
| | SINKS DISCHARGING INTO THE GREASE WASTE LINE WHICH IS |
| | NOT ALLOWED- SEC. 1003.3.1 FBC P. HANDSINKS ARE NOT |
| | CONSIDERED TO BE SIGNIFICANT CONTRIBUTORS OF GREASE |
| | WASTE. |
| | |
| | 8) FAILED. P0.02, P3.01: INDICATE THE WATER SUPPLY |
| | TEMPERATURE FOR THE EYE WASH STATION EW-2 WILL BE |
| | CONTROLLED BY A TEMPERATURE ACTUATED MIXING VALVE |
| | COMPLYING WITH ASSE 1071- SEC. 411.3 FBC P. |
| | TEPID WATER AND ASSE 1071 COMPLIANCE NOT NOTED IN THE |
| | SCHEDULE ON SHEET P0.02. |
| | |
| | 9) FAILED. P3.00, P3.01, & P3.02: IN ORDER TO MEET |
| | COMPLIANCE WITH TABLE C404.5.1 FBC ENERGY, THE HW |
| | RECIRCULATION LINES MUST BE LOCATED AT A POINT WITHIN 2 |
| | FT. OF THE HW SUPPLY PIPES TO THE PUBLIC LAVATORIES. |
| | THIS INCLUDES ALL BATHROOMS FOR STAFF BUT NOT THE |
| | PATIENT BATHROOMS. |
| | REFER TO COMMENT RESPONSE TO 6 AND IDENTIFY THE |
| | LOCATIONS OF THE PUBLIC LAVATORIES ON THE WATER RISER. |
| | |
| | |
| | 12) FAILED. P6.00: SHOW THE LOCATION OF THE THERMAL |
| | EXPANSION CONTROL DEVICE FOR THE ST-1- SEC. 607.3 FBC |
| | P. NOT PROVIDED. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |