| 2023-04-17 15:36:41 | 2ND REVIEW FBC-2020 FUEL GAS |
| | PERMIT- 23011089 |
| | 4/17/23 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | NFPA- 58- 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) 2ND REQUEST FOR A SEPARATE PERMIT APPLICATION AND |
| | PLANS FOR THE LP TANK TO BE SUBMITTED- SEC. 105.1 & |
| | 107.2.1 WPB. |
| | |
| | 2) REVISE THE CIVIL PLANS TO SHOW THE NEW LP TANK |
| | LOCATION AND EXTERIOR PIPING RUN TO THE BUILDING- SEC. |
| | 107.2.1 WPB. |
| | |
| | 3) THE ENGINEER???S RESPONSE TO 1ST REVIEW GAS PIPING |
| | COMMENTS REFERENCES SHEET P0.01 WHICH PROVIDES |
| | INCORRECT GAS PIPING COMPLIANCE INFORMATION. PLEASE |
| | CORRECT PER ITEMS BELOW. |
| | A) NATURAL GAS PIPING SIZING SHALL BE BASED ON THE FBC |
| | -2020 FUEL GAS CODE. |
| | B) LP GAS PIPING SHALL BE BASED ON FBC-2020 FUEL GAS |
| | AND NFPA 58- 2017. |
| | C) LP GAS PIPE SIZING IS NOT BASED ON TABLE 402.4(2) OF |
| | THE IFGC. TABLE 402.4(2) IS A NATURAL GAS TABLE. |
| | D) LP GAS PIPING DOES NOT RUN FROM THE TANK TO THE |
| | METER (THERE IS NO LP METER SHOWN) AND IS NOT 300 FT. |
| | LONG- REFER TO RISER DRAWING ON P7.02. |
| | D) LP GAS PIPING DOES NOT RUN 100 FT ON HOUSE SIDE OF |
| | THE METER (THERE IS NO LP METER SHOWN) AND THE 100 FT. |
| | LENGTH IS NOT SHOWN ON THE RISER. |
| | |
| | 4) SHEETS P7.02 NEW GAS RISER: PROVIDE THE MISSING GAS |
| | PIPING INFORMATION PREVIOUSLY REQUESTED UNDER 1ST |
| | REVIEW COMMENT #2. |
| | A) TYPES OF PIPING. |
| | B) TOTAL DEVELOPED LENGTHS OF EACH SYSTEM FROM THE TANK |
| | OR METER TO THE MOST REMOTE APPLIANCE OUTLET OR LOW |
| | PRESSURE REGULATOR. |
| | C) LOCATIONS OF REGULATORS AND SHUT OFF VALVES. |
| | D) LOW PRESSURE BRANCH AND CUT PIPING LENGTHS FROM THE |
| | REGULATORS TO THE BOILERS. |
| | E) PIPE SIZING TABLES. |
| | F) REGULATOR VENTING DETAILS |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |
| | |