2023-04-17 13:37:11THIS PLAN WAS REVIEWED AND FAILED BY CAITLIN L.
 FRANCIS, FIRE INVESTIGATOR, WITH THE FOLLOWING
 COMMENTS:
  
 THE COMMENTS BELOW ARE REPEATED COMMENTS FROM THE FIRST
 REVIEW, NO RESPONSES WERE FOUND IN THE DOCUMENTS
 SUBMITTED RESPONDING TO THE COMMENTS BELOW.
  
 1) ON THE COVER SHEET YOU REFERENCE 2020 NATIONAL FIRE
 CODE AND THE MOST CURRENT IS NFPA 2018.
  
 2) IN REFERENCE TO NPFA 101 CHAPTER 18 TABLE 18.1.6.1,
 WHAT CLASSIFICATION WOULD YOU SELECT TO APPLY TOWARD
 YOUR CONSTRUCTION TYPE?
  
 3) WHAT IS THE RATING OF THE FIRE SEPARATION INDICATED
 ON 016 A5.00?
  
 4) PLEASE CLARIFY THE PERCENTAGE OF REHABILITATION
 BEING DONE IN ACCORDANCE WITH NFPA 101 CHAPTER 18,
 18.1.1.4.3 REHABILITATION.
 18.1.1.4.3.1 FOR PURPOSES OF THE PROVISIONS OF THIS
 CHAPTER, THE FOLLOWING
 SHALL APPLY:
 (1) A MAJOR REHABILITATION SHALL INVOLVE THE
 MODIFICATION OF MORE THAN
 50 PERCENT, OR MORE THAN 4500 FT2 (420 M2), OF THE AREA
 OF THE SMOKE
 COMPARTMENT.
 (2) A MINOR REHABILITATION SHALL INVOLVE THE
 MODIFICATION OF NOT MORE THAN 50 PERCENT, AND NOT MORE
 THAN 4500 FT2 (420 M2), OF THE AREA OF THE SMOKE
 COMPARTMENT.
  
 5) PROVIDE THE HORIZONTAL EXIT CAPACITY AND TOTAL
 EGRESS CAPACITY OF ANY OTHER EXITS FOR EACH COMPARTMENT
 IN ACCORDANCE WITH NFPA 101 CHAPTER 18,
 18.2.2.5 HORIZONTAL EXITS. HORIZONTAL EXITS COMPLYING
 WITH 7.2.4 AND
 THE MODIFICATIONS OF 18.2.2.5.1 THROUGH 18.2.2.5.7
 SHALL BE PERMITTED.
 18.2.2.5.1 ACCUMULATION SPACE SHALL BE PROVIDED IN
 ACCORDANCE WITH
 18.2.2.5.1.1 AND 18.2.2.5.1.2.
 18.2.2.5.1.1 NOT LESS THAN 30 NET FT2 (2.8 NET M2) PER
 PATIENT IN A HOSPITAL
 OR NURSING HOME, OR NOT LESS THAN 15 NET FT2 (1.4 NET
 M2) PER RESIDENT IN
 A LIMITED CARE FACILITY, SHALL BE PROVIDED WITHIN THE
 AGGREGATED AREA OF
 CORRIDORS, PATIENT ROOMS, TREATMENT ROOMS, LOUNGE OR
 DINING AREAS, AND
 OTHER SIMILAR AREAS ON EACH SIDE OF THE HORIZONTAL
 EXIT.
 18.2.2.5.1.2 ON STORIES NOT HOUSING BEDRIDDEN OR
 LITTERBORNE PATIENTS,
 NOT LESS THAN 6 NET FT2 (0.56 NET M2) PER OCCUPANT
 SHALL BE PROVIDED ON
 EACH SIDE OF THE HORIZONTAL EXIT FOR THE TOTAL NUMBER
 OF OCCUPANTS IN
 ADJOINING COMPARTMENTS.
 18.2.2.5.2 THE TOTAL EGRESS CAPACITY OF THE OTHER EXITS
 (STAIRS, RAMPS,
 DOORS LEADING OUTSIDE THE BUILDING) SHALL NOT BE
 REDUCED BELOW ONE-THIRD
 OF THAT REQUIRED FOR THE ENTIRE AREA OF THE BUILDING.
  
 6) PLEASE PROVED THE MEASUREMENT OF THE WIDTH OF THE
 CORRIDORS PER NFPA 101 CHAPTER 18, 18.2.3.4.
  
 7) PLEASE PROVIDE THE MEASUREMENT OF THE DOOR WIDTH PER
 NFPA 101 CHAPTER 18,
 18.2.3.6 THE MINIMUM CLEAR WIDTH FOR DOORS IN THE MEANS
 OF EGRESS
 FROM SLEEPING ROOMS; DIAGNOSTIC AND TREATMENT AREAS,
 SUCH AS X-RAY,
 SURGERY, OR PHYSICAL THERAPY; AND NURSERY ROOMS SHALL
 BE AS FOLLOWS:
 (1) HOSPITALS AND NURSING HOMES ??? 411???2 IN. (1055
 MM)
 (2) PSYCHIATRIC HOSPITALS AND LIMITED CARE
 FACILITIES??? 32 IN. (810 MM)
  
 8) COMPLETE LIFE SAFETY PLANS FOR EACH OCCUPANCY SHALL
 BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL
 DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS,
 EXIT SIGNS, EMERGENCY LIGHTING, EXITS LEADING TO A
 PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE
 SAFETY FEATURES AND EQUIPMENT
  
  
 9) NO COMMON PATH OF TRAVEL WAS INDICATED ON THE PLANS.
  
  
  
 10) COMPARTMENT D HAS MULTIPLE EGRESS PATHS MARKED
 GOING THROUGH INTERVENING ROOMS OR SPACES WHICH IS NOT
 ALLOWED PER NFPA 101 CHAPTER 18,
  
 18.2.5.4* INTERVENING ROOMS OR SPACES. EVERY CORRIDOR
 SHALL PROVIDE
 ACCESS TO NOT LESS THAN TWO APPROVED EXITS IN
 ACCORDANCE WITH SECTIONS
 7.4 AND 7.5 WITHOUT PASSING THROUGH ANY INTERVENING
 ROOMS OR
 SPACES OTHER THAN CORRIDORS OR LOBBIES.
 A.18.2.5.4 THE TERM INTERVENING ROOMS OR SPACES MEANS
 ROOMS OR
 SPACES SERVING AS A PART OF THE REQUIRED MEANS OF
 EGRESS FROM ANOTHER ROOM.
  
 11) PLEASE ENSURE THAT THE SLEEPING SUITE TRAVEL
 DISTANCE IS IN ACCORDANCE WITH NFPA 101 CHAPTER 18,
 18.2.5.7.2.4 SLEEPING SUITE TRAVEL DISTANCE.
 (A) TRAVEL DISTANCE BETWEEN ANY POINT IN A SLEEPING
 SUITE AND AN EXIT
 ACCESS DOOR TO ANOTHER SUITE, AN EXIT ACCESS CORRIDOR
 DOOR, OR A HORIZONTAL
 EXIT DOOR FROM THAT SUITE SHALL NOT EXCEED 100 FT (30
 M).
 (B) TRAVEL DISTANCE BETWEEN ANY POINT IN A SLEEPING
 SUITE AND AN EXIT
 SHALL NOT EXCEED 200 FT (61 M).
  
 12) ACCORDING TO THE FOLLOWING CODE NOT LESS THEN TWO
 EXITS ARE REQUIRED. PLEASE INDICATE THE EXITS FROM EACH
 AREA AND THE TRAVEL DISTANCE FOR BOTH.
 18.2.4 NUMBER OF MEANS OF EGRESS.
 18.2.4.1 THE NUMBER OF MEANS OF EGRESS SHALL BE IN
 ACCORDANCE WITH
 SECTION 7.4.
 18.2.4.2 NOT LESS THAN TWO EXITS SHALL BE PROVIDED ON
 EVERY STORY.
 18.2.4.3 NOT LESS THAN TWO SEPARATE EXITS SHALL BE
 ACCESSIBLE FROM EVERY
 PART OF EVERY STORY.
 18.2.4.4* EXITS FROM SMOKE COMPARTMENTS.
 A.18.2.4.4 AN EXIT IS NOT NECESSARY FOR EACH INDIVIDUAL
 SMOKE COMPARTMENT
 IF THERE IS ACCESS TO AN EXIT THROUGH OTHER SMOKE
 COMPARTMENTS
 WITHOUT PASSING THROUGH THE SMOKE COMPARTMENT OF FIRE
 ORIGIN.
 18.2.4.4.1 NOT LESS THAN TWO EXITS SHALL BE ACCESSIBLE
 FROM EACH SMOKE
 COMPARTMENT, AND EGRESS SHALL BE PERMITTED THROUGH AN
 ADJACENT
 COMPARTMENT(S), PROVIDED THAT THE TWO REQUIRED EGRESS
 PATHS ARE ARRANGED
 SO THAT BOTH DO NOT PASS THROUGH THE SAME ADJACENT
 SMOKE
 COMPARTMENT.
 18.2.4.4.2 A DOOR IN A SMOKE BARRIER SHALL NOT SERVE AS
 THE ONLY EXIT
 ACCESS FROM ANY SPACE IN A SMOKE COMPARTMENT.
  
  
  
 13) THE MOUNTING OF EMERGENCY EXIT SIGNS MUST BE OVER
 THE DOOR IN WHICH THE EGRESS PATHWAY GOES PER NFPA 101
 CHAPTER 7, 7.10.1.9 MOUNTING LOCATION
  
  
  
  
  
  
  
  
  
  
  
  
  
  
 14) ROOM 1316 (HOUSE KEEPING STORAGE), 1035
 (MAINTENANCE SHOP) AND ALL SOILED ROOMS DO NOT SHOW
 FIRE RESISTANCE RATING. IF THESE ROOMS MEET THE
 REQUIREMENTS IN THE FOLLOWING CODE FROM NFPA 101
 CHAPTER 18 THEY MUST HAVE FIRE RESISTANCE RATING OR
 SMOKE PARTITIONS.
 18.3.2.1.2THE FOLLOWING AREAS SHALL BE CONSIDERED
 HAZARDOUS AREAS AND
 SHALL BE PROTECTED BY FIRE BARRIERS HAVING A MINIMUM
 1-HOUR FIRE RESISTANCE
 RATING IN ACCORDANCE WITH SECTION 8.3:
 (1) BOILER AND FUEL-FIRED HEATER ROOMS
 (2) CENTRAL/BULK LAUNDRIES LARGER THAN 100 FT2 (9.3 M2)
 (3) PAINT SHOPS EMPLOYING HAZARDOUS SUBSTANCES AND
 MATERIALS IN QUANTITIES
 LESS THAN THOSE THAT WOULD BE CLASSIFIED AS A SEVERE
 HAZARD
 (4) PHYSICAL PLANT MAINTENANCE SHOPS
 (5) ROOMS WITH SOILED LINEN IN VOLUME EXCEEDING 64 GAL
 (242 L)
 (6) ROOMS WITH COLLECTED TRASH IN VOLUME EXCEEDING 64
 GAL (242 L)
 (7) STORAGE ROOMS LARGER THAN 100 FT2 (9.3 M2) AND
 STORING COMBUSTIBLE
 MATERIAL
 18.3.2.1.3 THE FOLLOWING AREAS SHALL BE CONSIDERED
 HAZARDOUS AREAS AND
 SHALL BE PROTECTED BY SMOKE PARTITIONS IN ACCORDANCE
 WITH SECTION 8.4:
 (1) LABORATORIES EMPLOYING FLAMMABLE OR COMBUSTIBLE
 MATERIALS IN
 QUANTITIES LESS THAN THOSE THAT WOULD BE CONSIDERED A
 SEVERE
 HAZARD
 (2) STORAGE ROOMS LARGER THAN 50 FT2 (4.6 M2) BUT NOT
 EXCEEDING 100 FT2
 (9.3 M2) AND STORING COMBUSTIBLE MATERIAL
 (9.4
  
 15) IT IS INDICATED YOU ARE INSTALLING VINYL AND
 CARPET FLOORING. ALL FLOORING MUST HAVE SPECS SUBMITTED
 FOR REVIEW.
 10.2.7* INTERIOR FLOOR FINISH TESTING AND
 CLASSIFICATION.
 10.2.7.1* CARPET AND CARPET LIKE INTERIOR FLOOR
 FINISHES SHALL
 COMPLY WITH ASTM D 2859, STANDARD TEST METHOD FOR
 IGNITION
 CHARACTERISTICS OF FINISHED TEXTILE FLOOR COVERING
 MATERIALS.
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2
 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL
 HAVE A
 MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2.
  
 10.2.7.4 INTERIOR FLOOR FINISHES SHALL BE GROUPED IN
 THE CLASSES SPECIFIED
 IN 10.2.7.4.1 AND 10.2.7.4.2 IN ACCORDANCE WITH THE
 CRITICAL RADIANT FLUX
 REQUIREMENTS.
 10.2.7.4.1 CLASS I INTERIOR FLOOR FINISH. CLASS I
 INTERIOR FLOOR FINISH
 SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN
 0.45 W/CM2, AS DETERMINED
 BY THE TEST DESCRIBED IN 10.2.7.3.
 10.2.7.4.2 CLASS II INTERIOR FLOOR FINISH. CLASS II
 INTERIOR FLOOR FINISH
 SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN
 0.22 W/CM2, BUT LESS
 THAN 0.45 W/CM2, AS DETERMINED BY THE TEST DESCRIBED IN
 10.2.7.3.
  
 PLEASE REVIEW AND PROVIDE SPEC SHEETS.
  
  
 16) ON SHEET 047 AC1.03 THERE ARE DIFFERENT LEVELS OF
 SECURITY. PLEASE INDICATE THE TYPE OF DOOR CLOSING OR
 LOCKING MECHANISMS ON EACH LEVEL OF SECURITY. HOW DO
 PATIENTS EGRESS IN A FIRE EMERGENCY?
  
  
  
  
  
 17) PLEASE ENSURE THAT THE SLEEPING SUITE SUPERVISION
 MEETS THE REQUIREMENTS OF NFPA 101 CHAPTER 18,
 18.2.5.7.2.1 SLEEPING SUITE SUPERVISION.
 (A) SLEEPING SUITES SHALL BE PROVIDED WITH CONSTANT
 STAFF SUPERVISION
 WITHIN THE SUITE.
 (B)* SLEEPING SUITES SHALL BE ARRANGED IN ACCORDANCE
 WITH ONE OF THE
 FOLLOWING:
 (1)* PATIENT SLEEPING ROOMS WITHIN SLEEPING SUITES
 SHALL PROVIDE ONE OF
 THE FOLLOWING:
 (A) THE PATIENT SLEEPING ROOMS SHALL BE ARRANGED TO
 ALLOW FOR
 DIRECT SUPERVISION FROM A NORMALLY ATTENDED LOCATION
 WITHIN
 THE SUITE, SUCH AS IS PROVIDED BY GLASS WALLS, AND
 CUBICLE CURTAINS
 SHALL BE PERMITTED.
 (B) ANY PATIENT SLEEPING ROOMS WITHOUT THE DIRECT
 SUPERVISION
 REQUIRED BY 18.2.5.7.2.1(B)(1)(A) SHALL BE PROVIDED
 WITH
 SMOKE DETECTION IN ACCORDANCE WITH SECTION 9.6 AND
 18.3.4.
 (2) SLEEPING SUITES SHALL BE PROVIDED WITH A TOTAL
 (COMPLETE) COVERAGE
 AUTOMATIC SMOKE DETECTION SYSTEM IN ACCORDANCE WITH
 9.6.2.9 AND
 18.3.4
  
 18) ANY REMOVAL AND/OR CONSTRUCTION OF THE CEILING/WALL
 AREAS MAY REQUIRE AN EVALUATION OR MODIFICATION OF THE
 FIRE SPRINKLER AND FIRE ALARM SYSTEMS FOR CODE COVERAGE
 AND COMPLIANCE BY CERTIFIED CONTRACTORS.
  
 19) ANY AND ALL WORK ON THE FIRE SPRINKLER AND/OR FIRE
 ALARM SYSTEMS SHALL BE DONE UNDER SEPARATE PERMITS AND
 SHOP DRAWINGS BY CERTIFIED CONTRACTORS.
  
 20) IF ACCESS CONTROL IS BEING UPDATED OR ADDED THERE
 MUST BE A PERMIT AND PLAN SUBMITTED SEPARATELY.
  
 21) IF THE HOOD SYSTEM/ HOOD SUPPRESSION IS BEING
 UPDATED OR ADDED THERE MUST BE A PERMIT AND PLAN
 SUBMITTED SEPARATELY.
  
 ALL RESPONSES SHOULD BE IN A NARRATIVE FORM AND ANY AND
 ALL CHANGES MUST B CLOUDED ON THE PLANS FOR RESUBMITTAL
 VIA BUILDING DEPARTMENT.
  
 CAITLIN L. FRANCIS
 FIRE INVESTIGATOR
 WEST PALM BEACH FIRE RESCUE