| 2023-04-24 14:01:13 | HOSPITAL REMODEL |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | |
| | 1) DRAWING G0.00 SHOWS RISK CATEGORY IV - DRAWING S1.10 |
| | SHOWS RISK CATEGORY III - PLEASE CLARIFY - THEY SHOULD |
| | MATCH. |
| | |
| | 2) PLEASE PROVIDE THE FLORIDA STATE PRODUCT APPROVAL |
| | FRONT PAGES FOR PRODUCT APPROVALS (FL15850) - (FL8787) |
| | - (FL4553) - ALL PRODUCT APPROVALS NEED TO BE REVIEWED |
| | AND MARKED APPROVED BY THE BUILDING DESIGNER OF RECORD |
| | FBC WPB 107.3.4 |
| | |
| | 3) PLEASE NOTE WHICH ROOMS ARE TO BE ACCESSIBLE ROOMS |
| | ON THE DRAWINGS - FBC A 223.2.1 FACILITIES NOT |
| | SPECIALIZING IN TREATING CONDITIONS THAT AFFECT |
| | MOBILITY. |
| | IN FACILITIES NOT SPECIALIZING IN TREATING CONDITIONS |
| | THAT AFFECT MOBILITY, AT LEAST 10 PERCENT, BUT NO FEWER |
| | THAN ONE, OF THE PATIENT SLEEPING ROOMS SHALL PROVIDE |
| | MOBILITY FEATURES COMPLYING WITH 805. ACCESSIBLE |
| | PATIENT BEDROOMS SHALL BE DISPERSED IN A MANNER THAT IS |
| | PROPORTIONATE BY TYPE OF MEDICAL SPECIALTY. FBC A |
| | 223.2.2 FACILITIES SPECIALIZING IN TREATING CONDITIONS |
| | THAT AFFECT MOBILITY. |
| | IN FACILITIES SPECIALIZING IN TREATING CONDITIONS THAT |
| | AFFECT MOBILITY, 100 PERCENT OF THE PATIENT SLEEPING |
| | ROOMS SHALL PROVIDE MOBILITY FEATURES COMPLYING WITH |
| | 805. |
| | |
| | 4) PLEASE SHOW THE FIRE RATED CEILING ASSEMBLY DESIGN |
| | NUMBER - FBC 703.3 |
| | |
| | 5) PLEASE SHOW THE FIRE RATED WALL ASSEMBLY DESIGN |
| | NUMBER ON THE WALL SCHEDULE - FBC 703.3 |
| | |
| | 6) CANNOT FIND THE DOOR HARDWARE SET DESCRIPTIONS - FBC |
| | WPB 107.2.1 |
| | |
| | 7) THE PLYWOOD ADDED TO THE EXTERIOR WALLS SHOULD BE |
| | FIRE RETARDANT PER FBC 602.3 |
| | |
| | 8) THE STRUCTURAL DRAWINGS DO NOT SHOW AS DIGITALLY |
| | SIGNED IN ADOBE READER - SIGNED AND SEALED DRAWINGS IN |
| | PROJECTDOX NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED |
| | TO BE USED IN ELECTRONIC PLAN REVIEW. (A |
| | CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED |
| | A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF |
| | E-SIGNATURE). |
| | |
| | |
| | |
| | |
| | |
| | |