| 2023-02-23 11:03:13 | 1ST REVIEW FMC |
| | PERMIT: 23011089 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE DESIGN OF THIS PROJECT MUST MEET THE |
| | REQUIREMENTS OF ASHRAE 170-2013. FMC 407.1 |
| | |
| | 2) ARE THE MECHANICAL SYSTEMS LIKE FOR LIKE CHANGE |
| | OUTS? IF SO ADD A NOTE ON THE DRAWINGS STATING WHICH |
| | ARE AND WHICH ARE NEW SYSTEMS. ALL NEW SYSTEMS MUST |
| | INCLUDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS. |
| | FEC C403.2.1 |
| | |
| | 3) SHEETS M2.02A; ZM2.02B, M2.02C; PROVIDE A DESIGN |
| | THAT MINIMIZES THE SMOKE BARRIER PENETRATIONS |
| | REQUIREMENTS OF ASHRAE 170-2013 6.7.3 AND 6.7.4 AND |
| | SHOW THE REQUIRED SMOKE DAMPERS ON THE MECHANICAL |
| | DRAWINGS WHERE THE DUCTWORK PENETRATES THE SMOKE |
| | BARRIERS. |
| | |
| | 4) SHOW THE RADIATION DAMPERS FOR THE RETURNS AND THE |
| | EXHAUST FANS IN THE PATIENT ROOMS AND BATHROOMS. FMC |
| | 607.5.7 |
| | |
| | 5) PROVIDE A NOTE ON THE MECHANICAL DRAWING STATING |
| | THAT THE KITCHEN HOODS AND GREASE DUCTS WILL REQUIRE A |
| | SEPARATE PERMIT, DOCUMENT SUBMITTAL AND PLAN REVIEW AS |
| | THEY WILL NOT BE REVIEWED FROM THIS SUBMITTAL. |
| | |
| | 6) PROVIDE A NOTE ON THE MECHANICAL DRAWING STATING |
| | THAT THE REFRIGERATION SYSTEMS I.E. WALK-IN COOLERS AND |
| | FREEZERS WILL REQUIRE A SEPARATE PERMIT, DOCUMENT |
| | SUBMITTAL AND PLAN REVIEW AS THEY WILL NOT BE REVIEWED |
| | FROM THIS SUBMITTAL. |
| | |
| | 7) SHOW HOW THE VAV???S WILL HAVE ACCESS FOR |
| | MAINTENANCE AND CHANGE OUT. FMC 306.1 |
| | |
| | 8) SHEET M2-00-C: SHOW THE DAMPERS FOR THE PENETRATIONS |
| | IN THE RATED WALLS AT THE LAUNDRY. FMC 607. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |