Plan Review Notes
Plan Review Notes For Permit 23011089
Permit Number 23011089
Review Stop B
Sequence Number 1
Notes
Date Text
2023-03-10 11:30:20HOSPITAL REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) DRAWING G0.00 - UNDER "PROJECT INFORMATION" SHOWS
 RISK CATEGORY IV AND A WIND SPEED OF 178MPH - WIND
 SPEED SHOULD BE 180MPH PER FBC WPB SECTION 120.
  
 2) DRAWING G0.00 SHOWS RISK CATEGORY IV - DRAWING S1.10
 SHOWS RISK CATEGORY III - PLEASE CLARIFY - THEY SHOULD
 MATCH.
  
 3) DRAWING G0.00 - UNDER "PROJECT INFORMATION" THE FIRE
 RATINGS SHOULD BE SHOWN PER FBC TABLE 601 FOR A
 CONSTRUCTION TYPE III A.
  
 4) DRAWINGS SHOW OCCUPANCY TYPE "I 2" PLEASE SHOW IF
 CONDITION 1 OR CONDITION 2 - FBC 308.4
  
 5) PLEASE SHOW THE CORRIDOR WALLS TO BE SMOKE
 PARTITIONS PER FBC 407.3
 407.2 CORRIDORS CONTINUITY AND SEPARATION.
 CORRIDORS IN OCCUPANCIES IN GROUP I-2 SHALL BE
 CONTINUOUS TO THE EXITS AND SHALL BE SEPARATED FROM
 OTHER AREAS IN ACCORDANCE WITH SECTION 407.3 EXCEPT
 SPACES CONFORMING TO SECTIONS 407.2.1 THROUGH 407.2.6.
  
 6) PLEASE SHOW SMOKE PARTITION DETAILS PER FBC 710.4
 CONTINUITY.
 SMOKE PARTITIONS SHALL EXTEND FROM THE TOP OF THE
 FOUNDATION OR FLOOR BELOW TO THE UNDERSIDE OF THE FLOOR
 OR ROOF SHEATHING, DECK OR SLAB ABOVE OR TO THE
 UNDERSIDE OF THE CEILING ABOVE WHERE THE CEILING
 MEMBRANE IS CONSTRUCTED TO LIMIT THE TRANSFER OF SMOKE.
  
 7) WALLS SURROUNDING THE LAUNDRY ROOM (1209) ARE SHOWN
 TO BE FIRE RATED BUT THE DOOR IS NOT - PLEASE CLARIFY
 FBC TABLE 716.5
  
 8) PLEASE SHOW THE PUBLIC RESTROOM WALL AND BASE BOARD
 FINISHES TO COMPLY WITH FBC 1210.2.2 WALLS AND
 PARTITIONS.
 WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE
 SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS
 THAN 4 FEET (1219 MM) ABOVE THE FLOOR, (DRYWALL IS NOT
 CONSIDERED A HARD SURFACE)
  
 9) PLEASE PROVIDE A STATEMENT ON THE DRAWINGS FOR THE
 INTERIOR FINISHES - FBC 803.11 INTERIOR FINISH
 REQUIREMENTS BASED ON GROUP.
 INTERIOR WALL AND CEILING FINISH SHALL HAVE A FLAME
 SPREAD INDEX NOT GREATER THAN THAT SPECIFIED IN TABLE
 803.11 FOR THE GROUP AND LOCATION DESIGNATED.
  
 10) DRAWING A5.10 SHOWS A VAPER BARRIER AND FIRE
 SEPARATION AT THE ROOF TRUSSES - PLEASE CLARIFY - WHAT
 TYPE OF VAPER BARRIER AND THE HOURLY FIRE RATING -
 PLEASE PROVIDE DETAILS - ROOF VENTILATION MAY BE NEEDED
 PER FBC 1203.2 VENTILATION REQUIRED. ENCLOSED ATTICS
 AND ENCLOSED RAFTER SPACES FORMED WHERE CEILINGS ARE
 APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF FRAMING
 MEMBERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE
 SPACE BY VENTILATION OPENINGS PROTECTED AGAINST THE
 ENTRANCE OF RAIN AND SNOW. BLOCKING AND BRIDGING SHALL
 BE ARRANGED SO AS NOT TO INTERFERE WITH THE MOVEMENT OF
 AIR. AN AIRSPACE OF NOT LESS THAN 1 INCH (25 MM) SHALL
 BE PROVIDED BETWEEN THE INSULATION AND THE ROOF
 SHEATHING. THE NET FREE VENTILATING AREA SHALL BE NOT
 LESS THAN 1/150 OF THE AREA OF THE SPACE VENTILATED.
  
 11) DRAWING A5.10 SHOW A FIRE SEPARATION AT THE ROOF
 TRUSSES - PLEASE CLARIFY - SHOW THE HOURLY FIRE RATING
 ASSEMBLY - PLEASE PROVIDE DETAILS - FBC 708.4
 CONTINUITY.
 FIRE PARTITIONS SHALL EXTEND FROM THE TOP OF THE
 FOUNDATION OR FLOOR/CEILING ASSEMBLY BELOW TO THE
 UNDERSIDE OF THE FLOOR OR ROOF SHEATHING, SLAB OR DECK
 ABOVE OR TO THE FIRE-RESISTANCE-RATED FLOOR/CEILING OR
 ROOF/CEILING ASSEMBLY ABOVE, AND SHALL BE SECURELY
 ATTACHED THERETO.
  
 12) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE NEW EXTERIOR WINDOWS AND
 DOORS - ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND
 MARKED APPROVED BY THE BUILDING DESIGNER OF RECORD FBC
 WPB 107.3.4
  
 13) PLEASE SHOW THE WATER DRAINAGE FROM THE CANOPY ROOF
 SYSTEM - FBC 1503.7 PROTECTION AGAINST DECAY AND
 TERMITES.
 CONDENSATE LINES AND ROOF DOWNSPOUTS SHALL DISCHARGE AT
 LEAST 1 FOOT (305 MM) AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EXTENSIONS, OR
 SPLASH BLOCKS.
 FBC 1808.7.4 "REQUIRED DRAINAGE TO THE POINT OF
 DISCHARGE AND AWAY FROM THE STRUCTURE IS PROVIDED AT
 ALL LOCATIONS ON THE SITE".
  
 14) THE VERTICAL TOILET GRAB BAR IS NOT A REQUIREMENT
 IN THE FBC - PLEASE SHOW THE 12 INCH CLEARANCE ABOVE
 THE GRAB BARS - FBC A 609.3 THE SPACE BETWEEN THE GRAB
 BAR AND PROJECTING OBJECTS ABOVE SHALL BE 12 INCHES
 (305 MM) MINIMUM.
  
 15) ACCESSIBLE RESTROOM = WHEN REFERRING TO THE
 DIMENSION FROM THE FLOOR TO THE BOTTOM OF THE MIRROR
 PLEASE USE THE WORDS "REFLECTIVE SURFACE" - FBC A 603.3
 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND
  
 16) PLEASE NOTE WHICH ROOMS ARE TO BE ACCESSIBLE ROOMS
 ON THE DRAWINGS - FBC A 223.2.1 FACILITIES NOT
 SPECIALIZING IN TREATING CONDITIONS THAT AFFECT
 MOBILITY.
 IN FACILITIES NOT SPECIALIZING IN TREATING CONDITIONS
 THAT AFFECT MOBILITY, AT LEAST 10 PERCENT, BUT NO FEWER
 THAN ONE, OF THE PATIENT SLEEPING ROOMS SHALL PROVIDE
 MOBILITY FEATURES COMPLYING WITH 805. ACCESSIBLE
 PATIENT BEDROOMS SHALL BE DISPERSED IN A MANNER THAT IS
 PROPORTIONATE BY TYPE OF MEDICAL SPECIALTY. FBC A
 223.2.2 FACILITIES SPECIALIZING IN TREATING CONDITIONS
 THAT AFFECT MOBILITY.
 IN FACILITIES SPECIALIZING IN TREATING CONDITIONS THAT
 AFFECT MOBILITY, 100 PERCENT OF THE PATIENT SLEEPING
 ROOMS SHALL PROVIDE MOBILITY FEATURES COMPLYING WITH
 805.
  
 17) PLEASE SHOW THE INCIDENTAL ROOMS (LAUNDRY, STORAGE,
 PATIENT ROOMS EQUIPPED WITH PADDED SURFACES, PHYSICAL
 PLANT MAINTENANCE SHOPS, WASTE AND LINEN COLLECTION,
 ETC) TO BE FIRE RATED PER FBC SECTION 509 - TABLE 509
 --- 509.4.1SEPARATION. WHERE TABLE 509 SPECIFIES A
 FIRE-RESISTANCE-RATED SEPARATION, THE INCIDENTAL USES
 SHALL BE SEPARATED FROM THE REMAINDER OF THE BUILDING
 BY A FIRE BARRIER CONSTRUCTED IN ACCORDANCE WITH
 SECTION 707 OR A HORIZONTAL ASSEMBLY CONSTRUCTED IN
 ACCORDANCE WITH SECTION 711, OR BOTH.
  
 18) SEPARATE PERMITS ARE REQUIRED FOR - GENERATOR,
 GENERATOR ENCLOSURE, OUTDOOR CANOPIES, PARKING LOT,
 FENCES.
  