| 2023-03-10 11:30:20 | HOSPITAL REMODEL |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | |
| | 1) DRAWING G0.00 - UNDER "PROJECT INFORMATION" SHOWS |
| | RISK CATEGORY IV AND A WIND SPEED OF 178MPH - WIND |
| | SPEED SHOULD BE 180MPH PER FBC WPB SECTION 120. |
| | |
| | 2) DRAWING G0.00 SHOWS RISK CATEGORY IV - DRAWING S1.10 |
| | SHOWS RISK CATEGORY III - PLEASE CLARIFY - THEY SHOULD |
| | MATCH. |
| | |
| | 3) DRAWING G0.00 - UNDER "PROJECT INFORMATION" THE FIRE |
| | RATINGS SHOULD BE SHOWN PER FBC TABLE 601 FOR A |
| | CONSTRUCTION TYPE III A. |
| | |
| | 4) DRAWINGS SHOW OCCUPANCY TYPE "I 2" PLEASE SHOW IF |
| | CONDITION 1 OR CONDITION 2 - FBC 308.4 |
| | |
| | 5) PLEASE SHOW THE CORRIDOR WALLS TO BE SMOKE |
| | PARTITIONS PER FBC 407.3 |
| | 407.2 CORRIDORS CONTINUITY AND SEPARATION. |
| | CORRIDORS IN OCCUPANCIES IN GROUP I-2 SHALL BE |
| | CONTINUOUS TO THE EXITS AND SHALL BE SEPARATED FROM |
| | OTHER AREAS IN ACCORDANCE WITH SECTION 407.3 EXCEPT |
| | SPACES CONFORMING TO SECTIONS 407.2.1 THROUGH 407.2.6. |
| | |
| | 6) PLEASE SHOW SMOKE PARTITION DETAILS PER FBC 710.4 |
| | CONTINUITY. |
| | SMOKE PARTITIONS SHALL EXTEND FROM THE TOP OF THE |
| | FOUNDATION OR FLOOR BELOW TO THE UNDERSIDE OF THE FLOOR |
| | OR ROOF SHEATHING, DECK OR SLAB ABOVE OR TO THE |
| | UNDERSIDE OF THE CEILING ABOVE WHERE THE CEILING |
| | MEMBRANE IS CONSTRUCTED TO LIMIT THE TRANSFER OF SMOKE. |
| | |
| | 7) WALLS SURROUNDING THE LAUNDRY ROOM (1209) ARE SHOWN |
| | TO BE FIRE RATED BUT THE DOOR IS NOT - PLEASE CLARIFY |
| | FBC TABLE 716.5 |
| | |
| | 8) PLEASE SHOW THE PUBLIC RESTROOM WALL AND BASE BOARD |
| | FINISHES TO COMPLY WITH FBC 1210.2.2 WALLS AND |
| | PARTITIONS. |
| | WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE |
| | SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, |
| | HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS |
| | THAN 4 FEET (1219 MM) ABOVE THE FLOOR, (DRYWALL IS NOT |
| | CONSIDERED A HARD SURFACE) |
| | |
| | 9) PLEASE PROVIDE A STATEMENT ON THE DRAWINGS FOR THE |
| | INTERIOR FINISHES - FBC 803.11 INTERIOR FINISH |
| | REQUIREMENTS BASED ON GROUP. |
| | INTERIOR WALL AND CEILING FINISH SHALL HAVE A FLAME |
| | SPREAD INDEX NOT GREATER THAN THAT SPECIFIED IN TABLE |
| | 803.11 FOR THE GROUP AND LOCATION DESIGNATED. |
| | |
| | 10) DRAWING A5.10 SHOWS A VAPER BARRIER AND FIRE |
| | SEPARATION AT THE ROOF TRUSSES - PLEASE CLARIFY - WHAT |
| | TYPE OF VAPER BARRIER AND THE HOURLY FIRE RATING - |
| | PLEASE PROVIDE DETAILS - ROOF VENTILATION MAY BE NEEDED |
| | PER FBC 1203.2 VENTILATION REQUIRED. ENCLOSED ATTICS |
| | AND ENCLOSED RAFTER SPACES FORMED WHERE CEILINGS ARE |
| | APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF FRAMING |
| | MEMBERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE |
| | SPACE BY VENTILATION OPENINGS PROTECTED AGAINST THE |
| | ENTRANCE OF RAIN AND SNOW. BLOCKING AND BRIDGING SHALL |
| | BE ARRANGED SO AS NOT TO INTERFERE WITH THE MOVEMENT OF |
| | AIR. AN AIRSPACE OF NOT LESS THAN 1 INCH (25 MM) SHALL |
| | BE PROVIDED BETWEEN THE INSULATION AND THE ROOF |
| | SHEATHING. THE NET FREE VENTILATING AREA SHALL BE NOT |
| | LESS THAN 1/150 OF THE AREA OF THE SPACE VENTILATED. |
| | |
| | 11) DRAWING A5.10 SHOW A FIRE SEPARATION AT THE ROOF |
| | TRUSSES - PLEASE CLARIFY - SHOW THE HOURLY FIRE RATING |
| | ASSEMBLY - PLEASE PROVIDE DETAILS - FBC 708.4 |
| | CONTINUITY. |
| | FIRE PARTITIONS SHALL EXTEND FROM THE TOP OF THE |
| | FOUNDATION OR FLOOR/CEILING ASSEMBLY BELOW TO THE |
| | UNDERSIDE OF THE FLOOR OR ROOF SHEATHING, SLAB OR DECK |
| | ABOVE OR TO THE FIRE-RESISTANCE-RATED FLOOR/CEILING OR |
| | ROOF/CEILING ASSEMBLY ABOVE, AND SHALL BE SECURELY |
| | ATTACHED THERETO. |
| | |
| | 12) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE |
| | INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE |
| | PRODUCT APPROVALS FOR THE NEW EXTERIOR WINDOWS AND |
| | DOORS - ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND |
| | MARKED APPROVED BY THE BUILDING DESIGNER OF RECORD FBC |
| | WPB 107.3.4 |
| | |
| | 13) PLEASE SHOW THE WATER DRAINAGE FROM THE CANOPY ROOF |
| | SYSTEM - FBC 1503.7 PROTECTION AGAINST DECAY AND |
| | TERMITES. |
| | CONDENSATE LINES AND ROOF DOWNSPOUTS SHALL DISCHARGE AT |
| | LEAST 1 FOOT (305 MM) AWAY FROM THE STRUCTURE SIDEWALL, |
| | WHETHER BY UNDERGROUND PIPING, TAIL EXTENSIONS, OR |
| | SPLASH BLOCKS. |
| | FBC 1808.7.4 "REQUIRED DRAINAGE TO THE POINT OF |
| | DISCHARGE AND AWAY FROM THE STRUCTURE IS PROVIDED AT |
| | ALL LOCATIONS ON THE SITE". |
| | |
| | 14) THE VERTICAL TOILET GRAB BAR IS NOT A REQUIREMENT |
| | IN THE FBC - PLEASE SHOW THE 12 INCH CLEARANCE ABOVE |
| | THE GRAB BARS - FBC A 609.3 THE SPACE BETWEEN THE GRAB |
| | BAR AND PROJECTING OBJECTS ABOVE SHALL BE 12 INCHES |
| | (305 MM) MINIMUM. |
| | |
| | 15) ACCESSIBLE RESTROOM = WHEN REFERRING TO THE |
| | DIMENSION FROM THE FLOOR TO THE BOTTOM OF THE MIRROR |
| | PLEASE USE THE WORDS "REFLECTIVE SURFACE" - FBC A 603.3 |
| | MIRRORS. |
| | MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL |
| | BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING |
| | SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH |
| | FLOOR OR GROUND |
| | |
| | 16) PLEASE NOTE WHICH ROOMS ARE TO BE ACCESSIBLE ROOMS |
| | ON THE DRAWINGS - FBC A 223.2.1 FACILITIES NOT |
| | SPECIALIZING IN TREATING CONDITIONS THAT AFFECT |
| | MOBILITY. |
| | IN FACILITIES NOT SPECIALIZING IN TREATING CONDITIONS |
| | THAT AFFECT MOBILITY, AT LEAST 10 PERCENT, BUT NO FEWER |
| | THAN ONE, OF THE PATIENT SLEEPING ROOMS SHALL PROVIDE |
| | MOBILITY FEATURES COMPLYING WITH 805. ACCESSIBLE |
| | PATIENT BEDROOMS SHALL BE DISPERSED IN A MANNER THAT IS |
| | PROPORTIONATE BY TYPE OF MEDICAL SPECIALTY. FBC A |
| | 223.2.2 FACILITIES SPECIALIZING IN TREATING CONDITIONS |
| | THAT AFFECT MOBILITY. |
| | IN FACILITIES SPECIALIZING IN TREATING CONDITIONS THAT |
| | AFFECT MOBILITY, 100 PERCENT OF THE PATIENT SLEEPING |
| | ROOMS SHALL PROVIDE MOBILITY FEATURES COMPLYING WITH |
| | 805. |
| | |
| | 17) PLEASE SHOW THE INCIDENTAL ROOMS (LAUNDRY, STORAGE, |
| | PATIENT ROOMS EQUIPPED WITH PADDED SURFACES, PHYSICAL |
| | PLANT MAINTENANCE SHOPS, WASTE AND LINEN COLLECTION, |
| | ETC) TO BE FIRE RATED PER FBC SECTION 509 - TABLE 509 |
| | --- 509.4.1SEPARATION. WHERE TABLE 509 SPECIFIES A |
| | FIRE-RESISTANCE-RATED SEPARATION, THE INCIDENTAL USES |
| | SHALL BE SEPARATED FROM THE REMAINDER OF THE BUILDING |
| | BY A FIRE BARRIER CONSTRUCTED IN ACCORDANCE WITH |
| | SECTION 707 OR A HORIZONTAL ASSEMBLY CONSTRUCTED IN |
| | ACCORDANCE WITH SECTION 711, OR BOTH. |
| | |
| | 18) SEPARATE PERMITS ARE REQUIRED FOR - GENERATOR, |
| | GENERATOR ENCLOSURE, OUTDOOR CANOPIES, PARKING LOT, |
| | FENCES. |
| | |