| 2023-04-04 08:50:12 | PETER E VALENTI |
| | BUILDING PLANS EXAMINER II/INSPECTOR |
| | [email protected] |
| | 561 805 6673 |
| | |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC M = FBC MECHANICAL |
| | FBC FG = FBC FUEL GAS |
| | |
| | 2ND BUILDING REVIEW DENIED: |
| | |
| | FBC B 107.2.1 & WPB AMENDMENTS TO FBC B 107.2.1, THE |
| | INFORMATION THAT HAS BEEN SUBMITTED IS NOT CLEAR. |
| | PLEASE ADDRESS THE FOLLOWING: |
| | |
| | 1.) PROVIDE AN OVERALL FLOOR PLAN TO IDENTIFY WHERE |
| | EACH UNIT IS INRELATION TO EACH OTHER AND THAT SHOWS |
| | EXTERIOR WALLS AND INTERIOR TENANT SEPARATION WALLS. |
| | THE OVERALL FLOOR PLAN DOES NOT MATCH THE UNIT LAYOUTS. |
| | PLEASE BE CLEAR AS TO THE ORIENTATION OF UNITS BY |
| | INDICATING NORTH, SOUTH, EAST, & WEST. ALSO INDICATE |
| | THE 2ND FLOOR ON LAYOUT SHEET. |
| | 2.) OK, MECHANICAL UNIT INFORMATION MUST BE APPROVED |
| | THROUGH MECHANICAL PERMIT #23031036. |
| | 3.) OK, WINDOWS/DOORS WERE APPROVED UNDER PERMIT |
| | #21120857. |
| | 4.) PROVIDE THE DETAILS FOR THE NEW SHOWER WORK |
| | INCLUDING LOCATION OF SHOWER WALLS IN RELATION TO |
| | EXTERIOR TENANT SEPARATION WALLS AND FLOOR/CEILING WORK |
| | FOR DUE TO SHOWERS. PROVIDE A WALL DETAIL SHOWING ALL |
| | MATERIAL TO BE USED INCLUDING FLOOR INSULATION, |
| | FRAMING, DRYWALL, & CEMENT BOARD. THIS MUST INCLUDE THE |
| | METHOD OF MAINTAINING THE FIRE RATING DETAILS SUCH AS |
| | USING THE DRYWALL WITH THE CEMENT BOARD ON SHOWER |
| | WALLS. |
| | 5.) THE VALUATION DOES NOT APPEAR TO BE ACCURATE IN |
| | ACCORDANCE WITH THE ICC BUILDING VALUATION DATA |
| | CONSTRUCTION COST SCHEDULE AND THE MARSHALL / SWIFT |
| | VALUATIONS. PLEASE RE-EVALUATE THE COST OF THIS PROJECT |
| | AND PROVIDE A BREAKDOWN OF COSTS OF ALL WORK. |
| | 6.) THE CONTRACTOR ON APPLICATION APPEARS TO BE A |
| | PLUMBING CONTRACTOR. FOR THIS PROJECT, PERMITS FOR |
| | MECHANICAL AND BUILDING PERMITS HAVE BEEN OBTAINED. |
| | THESE ADDITIONAL PERMITS (MECHANICAL 23031036 & |
| | BUILDING 23031034) MUST BE APPROVED. |
| | 7.) EACH PLAN SHEET SUBMITTED NEEDS TO BE SIGNED BY THE |
| | PERSON RESPONSIBLE FOR THE DESIGN. SEVERAL OF THE |
| | SUBMITTED SHEETS HAVE NOT BEEN SIGNED BY CONTRACTOR. |
| | PLAN SHEET IDENTIFIED AS "001 PLAN" (ELECTRICAL RISER) |
| | IS A COPY OF AN ORIGINAL HAND SIGNED/SEALED PLAN SHEET |
| | BY AN ARCHITECT. THIS MUST BE 3RD PARTY VERIFIED |
| | DIGITALLY SIGNATURE/SEAL BY ARCHITECT. PLEASE SEE THE |
| | SIGNATURE PLAN REVIEW NOTES. |