| Plan Review Notes For Permit 23011083 |
| Permit Number |
23011083 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-03-14 07:17:57 | 1ST REVIEW FMC | | | PERMIT: 23011083 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) OUR RECORDS DO NOT SHOW A MECHANICAL SYSTEM EVER | | | BEEN PERMITTED FOR THIS ADDRESS. NOTE 1 ON THE DRAWINGS | | | INDICATE 12,000 BTU. IS THIS A MECHANICAL SYSTEM? IF | | | SO, PROVIDE THE MECHANICAL EQUIPMENT SIZING | | | CALCULATIONS FOR THIS SYSTEM. IT WILL ALSO NEED TO | | | PROVIDE HEAT. FMC 312.1; 309.1 | | | | | | 2) PROVIDE MECHANICAL DRAWINGS THAT SHOW THE INDOOR | | | UNITS AND THE LOCATION OF THE CONDENSING UNITS. FBC | | | 107.3.5 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|