Plan Review Notes
Plan Review Notes For Permit 23011059
Permit Number 23011059
Review Stop SIGNATURE
Sequence Number 2
Notes
Date Text
2023-03-03 12:11:102ND DIGITAL SIGNATURE REVIEW
 PERMIT- 23011059
 3/3/23\
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS FP-001- FP-114: THE ENTIRE SET OF PLAN SHEETS
 UPLOADED DO NOT HAVE VERIFIABLE DIGITAL SIGNATURES AND
 SEALS BY THE ENGINEER OF RECORD AS REQUIRED BY FL.
 STATUTE 471.025 AND SEC. 61G15-23.005 FLORIDA
 ADMINISTRATIVE CODE. THE PLANS APPEAR TO HAVE SCANNED
 OR COPIED SEALS.
  
 2) THE SHEETS UPLOADED INTO THE SIGNATURE FILE SHOW A
 DIGITAL SIGNATURE SEAL ONLY ON THE COVER SHEET FP-001
 AND THERE IS NO ENGINEER'S TITLE BLOCK ON THE SHEET.
 PLEASE NOTE THE NEW SYSTEM EXCEEDS 49 HEADS WHICH
 REQUIRES A FL. LICENSED FIRE PROTECTION ENGINEER TO
 DESIGN THE SYSTEM- FL. STATUTE 633.102.
  
 FLORIDA BOARD OF PROFESSIONAL ENGINEERS GUIDELINES FOR
 ELECTRONIC OR DIGITALLY SIGNED AND SEALED PLANS AND
 DOCUMENTS.
 A DIGITAL SIGNATURE MUST BE UNIQUE TO THE PROFESSIONAL
 ENGINEER USING IT, OBTAINED FROM A THIRD-PARTY
 CERTIFICATION AUTHORITY, AND CAPABLE OF VERIFICATION.
 THE CERTIFICATION AUTHORITY WILL VET THE PE AND PROVIDE
 A PASSWORD-PROTECTED DIGITAL SIGNATURE FILE. (FBPE DOES
 NOT APPROVE OR PROVIDE A LIST OF AUTHORITIES.)
 YOU MAY NOT USE THE DIGITAL OPTION PROVIDED IN ADOBE
 ACROBAT, SINCE IT IS SELF-AUTHENTICATED AND DOES NOT
 USE A THIRD PARTY.
 YOUR DIGITAL SIGNATURE MUST BE LINKED TO THE DOCUMENT
 IN SUCH A WAY THAT ANY CHANGE INVALIDATES THE SIGNATURE
 AND DOCUMENT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  