| 2023-03-03 12:11:10 | 2ND DIGITAL SIGNATURE REVIEW |
| | PERMIT- 23011059 |
| | 3/3/23\ |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS FP-001- FP-114: THE ENTIRE SET OF PLAN SHEETS |
| | UPLOADED DO NOT HAVE VERIFIABLE DIGITAL SIGNATURES AND |
| | SEALS BY THE ENGINEER OF RECORD AS REQUIRED BY FL. |
| | STATUTE 471.025 AND SEC. 61G15-23.005 FLORIDA |
| | ADMINISTRATIVE CODE. THE PLANS APPEAR TO HAVE SCANNED |
| | OR COPIED SEALS. |
| | |
| | 2) THE SHEETS UPLOADED INTO THE SIGNATURE FILE SHOW A |
| | DIGITAL SIGNATURE SEAL ONLY ON THE COVER SHEET FP-001 |
| | AND THERE IS NO ENGINEER'S TITLE BLOCK ON THE SHEET. |
| | PLEASE NOTE THE NEW SYSTEM EXCEEDS 49 HEADS WHICH |
| | REQUIRES A FL. LICENSED FIRE PROTECTION ENGINEER TO |
| | DESIGN THE SYSTEM- FL. STATUTE 633.102. |
| | |
| | FLORIDA BOARD OF PROFESSIONAL ENGINEERS GUIDELINES FOR |
| | ELECTRONIC OR DIGITALLY SIGNED AND SEALED PLANS AND |
| | DOCUMENTS. |
| | A DIGITAL SIGNATURE MUST BE UNIQUE TO THE PROFESSIONAL |
| | ENGINEER USING IT, OBTAINED FROM A THIRD-PARTY |
| | CERTIFICATION AUTHORITY, AND CAPABLE OF VERIFICATION. |
| | THE CERTIFICATION AUTHORITY WILL VET THE PE AND PROVIDE |
| | A PASSWORD-PROTECTED DIGITAL SIGNATURE FILE. (FBPE DOES |
| | NOT APPROVE OR PROVIDE A LIST OF AUTHORITIES.) |
| | YOU MAY NOT USE THE DIGITAL OPTION PROVIDED IN ADOBE |
| | ACROBAT, SINCE IT IS SELF-AUTHENTICATED AND DOES NOT |
| | USE A THIRD PARTY. |
| | YOUR DIGITAL SIGNATURE MUST BE LINKED TO THE DOCUMENT |
| | IN SUCH A WAY THAT ANY CHANGE INVALIDATES THE SIGNATURE |
| | AND DOCUMENT. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |