2023-03-07 08:57:003/7/23 FAILED FOR THE FOLLOWING REASONS:
  
  
 1. PURSUANT TO SECTION 94-305(B)(4) OF THE ZLDR:
 MECHANICAL EQUIPMENT MAY NOT PROJECT MORE THAN 4 FEET
 INTO A REQUIRED SETBACK.
  
 REAR SETBACK FOR THE PRIMARY STRUCTURE IS REQUIRED TO
 BE 15 FEET OR 10% OF LOT DEPTH, WHICHEVER IS LESS
  
 REAR SETBACK FOR BLOOMFILED IS 13 FEET, THEREFORE
 GENERATOR MUST BE 9 FEET FROM THE REAR PROPERTY LINE
  