2023-03-15 18:55:17RESIDENTIAL (R3) BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #23011002
 130 BLOOMFIELD DR
  
 1- GENERATOR CONCRETE PAD ENGINEERING IS DESIGNED BASED
 ON 2017 FBC. ENGINEERING NEEDS TO BE REVISED USING ASCE
 -16 AND 2020 FBC WHICH IS THE CURRENT CODE. ENGINEER TO
 REVISE ENGINEERING DATA AS REQUIRED.
 CHAPTER 553 F.S.
  
 2- GENERATOR CONCRETE PAD ENGINEERING HAS A COPY OF THE
 ENGINEER'S DIGITAL SIGNATURE. NEED ORIGINAL
 SEAL/SIGNATURE WHEN SUBMITTED FOR PUBLIC RECORDS.
 ELECTRONIC SUBMITTALS NEED VERIFIABLE DIGITAL
 SIGNATURE.
  
 3- THE GENERATOR SHALL BE LOCATED A MINIMUM OF 10 FT.
 FROM ANY OPENING INCLUDING WINDOWS, DOORS, ETC. SEC.
 R303.5.1 FBC RES. PROVIDE NOTE ON SURVEY TO AVOID
 CONFLICTS AT TIME OF INSPECTION.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  