| 2023-01-26 11:00:33 | 1ST REVIEW FMC | | | PERMIT: 23010960 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) IF THIS CHANGE IS FOR THE R-1 UNITS, CLEARLY LABEL | | | THESE SHEETS AS SUCH. | | | | | | 2) PROVIDE THE DESIGN THAT SHOWS CODE COMPLIANCE FOR | | | THE CONTROLS OF THIS R-1 MECHANICAL SYSTEM . FEC | | | C403.2.4.8 | | | | | | 3) SHEET M3-16: EXPLAIN THE EXISTING 4 INCH DUCT | | | RUNNING ALONG SIDE THE BATH EXHAUST DUCT AND | | | TERMINATING OUTDOORS. IT APPEARS THAT IN THE EXISTING | | | DRAWING IT IS FOR ANOTHER BATH EXHAUST FAN THAT IS NOT | | | SHOWN IN THE PROPOSED PLAN. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|