| Plan Review Notes For Permit 23010960 |
| Permit Number |
23010960 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-01-26 11:39:07 | REVISION | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) DRAWING A3-00A - PLEASE SHOW THE DIMENSION FOR THE | | | REQUIRED TOE CLEARANCE AT THE BAR - FBC A 306.2.3 | | | MINIMUM REQUIRED DEPTH. | | | WHERE TOE CLEARANCE IS REQUIRED AT AN ELEMENT AS PART | | | OF A CLEAR FLOOR SPACE, THE TOE CLEARANCE SHALL EXTEND | | | 17 INCHES (430 MM) MINIMUM UNDER THE ELEMENT. |
|