| 2023-07-28 14:20:47 | RESIDENTIAL (R3) SECOND BUILDING AUDIT. |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #23010932 |
| | 841 29TH ST |
| | |
| | PREVIOUS COMMENT: |
| | 1- SOLAR PANELS LAYOUT DON'T SHOW COMPLIANCE WITH THE |
| | PATHWAYS REQUIRED BY SEC. R324.6.1 FBC-RESIDENTIAL. |
| | |
| | RESPONSE: |
| | SOLAR PANELS LAYOUT WAS REVISED. THE WORST CASE MODULE |
| | INFORMATION SHOWN ON SHEET S-1 NEEDS TO BE REVISED ALSO |
| | TO REFLECT THE NEW LAYOUT. ALSO, NEED TO REVISE THE |
| | WIDTH OF ROOF ZONE 2E. THIS DIMENSION IS 4' NOT 3' AS |
| | REQUIRED BY NOTE "A" ON FIGURE R301.2(7) |
| | FBC-RESIDENTIAL. IN ADDITION, SOME ROOF PANELS ARE |
| | LOCATED IN ROOF ZONE 2R. NEED TO ADD THIS ROOF ZONE TO |
| | THE WORST CASE MODULE CALCULATIONS. |
| | SEC. R301.2.1 FBC-RESIDENTIAL. |
| | |
| | 2- REVISED DRAWINGS WERE NOT SIGNED AND SEALED BY THE |
| | ENGINEER OF RECORD. |
| | ALL DRAWINGS NEED TO BE SIGNED AND SEALED AS REQUIRED |
| | BY CHAPTER 471 F.S. WHEN SUBMITTING DRAWINGS/DOCUMENTS |
| | FOR PUBLIC RECORDS. |
| | |
| | NOTE: |
| | TO HELP EXPEDITE THE AUDIT PROCESS PLEASE ADDRESS THE |
| | SIGNATURE REVIEW COMMENTS DONE ON THE PREVIOUS |
| | SIGNATURE REVIEW OF THIS PROJECT. |
| | |
| | SIGNATURE REVIEW |
| | A)DRAWINGS UPLOADED TO PROJECTDOX SEEM TO HAVE A COPY |
| | OF A DIGITAL SIGNATURE. DIGITAL SIGNATURES ARE NOT |
| | ALLOWED TO BE PRINTED. ALL DOCUMENTS PREPARED BY A |
| | LICENSED ENGINEER NEED TO HAVE THE ORIGINAL SEAL AND |
| | SIGNATURE OF THE ENGINEER OF RECORD AS REQUIRED BY SEC. |
| | 61G15-23.003 FAC AND CHAPTER 471 F.S. WHEN SUBMITTING |
| | PLANS/DOCUMENTS FOR PUBLIC RECORDS. |
| | |
| | B)ENGINEER'S DIGITAL SIGNATURE DOESN'T COMPLY WITH THE |
| | REQUIREMENTS OF FBPE. NEED A SEPARATE TEXT BOX WITH THE |
| | TEXT BOX LANGUAGE IDENTICAL TO THE SAMPLES SHOWN BY |
| | FBPE. |
| | SEE FBPE.ORG/LEGAL/SIGNING-AND-SEALING-ENGINEERING-DOCU |
| | MENTS/???.. AND REVISE DIGITAL SIGNATURE AS REQUIRED. |
| | NOTE: THIS WAS CONFIRMED WITH THE FBPE INVESTIGATOR. |
| | |
| | 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND |
| | SEALING ELECTRONICALLY TRANSMITTED PLANS, |
| | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. |
| | |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |
| | |