2023-01-26 16:37:111ST REVIEW FBC-2020 PLUMBING
 PERMIT- 23010924
 1/26/2023
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC B FLORIDA BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET CP1.0 NOTE 3: SHOW THE LOCATIONS OF REQUIRED
 DIAPER CHANGING TABLES IN THE POOL BATHROOMS- SEC.
 454.1.6.1.1 FBC B.
  
 2) CP1.0 NOTE 8: PLEASE SHOW THE DISTANCE MEASUREMENT
 FROM THE HOSE BIB TO THE MEN'S AND WOMEN'S RESTROOMS-
 SEC. 454.1.6.1.3 FBC B. MAXIMUM 25 FT. ALLOWABLE.
  
 3) CP1.0: THERE IS A NOTE BY THE POOL EQUIPMENT AREA
 THAT STATES- 4IN. WASTE LINE BY G.C. AND SHEET CP4.0
 SHOWS A WASTE DETAIL. PLEASE SHOW THE WASTE PIPE RUN ON
 THE PLAN AND DISCHARGE LOCATION. PLEASE NOTE SEC.
 90-205(1) WPB CODE OF ORDINANCES REQUIRES THE POOL
 WASTEWATER TO BE DECHLORINATED AND DRAIN INTO THE STORM
 SYSTEM AND NOT THE SANITARY SYSTEM. PLEASE NOTE THE
 FOLLOWING:
  
 SWIMMING POOL WATER SHALL NOT BE DISCHARGED TO SANITARY
 SEWER WITHOUT PRIOR APPROVAL FROM THE PUBLIC UTILITIES
 DEPARTMENT.
 SWIMMING POOL WATER MAY BE DISCHARGED TO THE CITY
 STORMWATER SEWER ONLY IF THE WATER IS DECHLORINATED
 ACCORDING TO SECTION 90-205(1) OF THE CITY OF WEST PALM
 BEACH CODE OF ORDINANCES. SUBMIT THE MANUFACTURER'S
 SPECIFICATION FOR THE DICHLORINATION SYSTEM FOR REVIEW
 AND STAMPING BEFORE THE INSPECTION. AT THE TIME OF POOL
 WATER DISCHARGE, THE FOLLOWING WILL BE REQUIRED:
 * THE RECEIVING INLET MUST BE PROTECTED (FILTER CLOTH
 TO KEEP EXCESS SEDIMENTS FROM ROADWAY WASHING INTO THE
 INLET).
 * NO DISCHARGE HOSE CAN BE DIRECTLY INSERTED INTO THE
 INLET TO DISCHARGE EFFLUENT.
 * WHENEVER POSSIBLE, DISCHARGE EFFLUENT SHALL BE
 ALLOWED TO FILTER THROUGH GRASS AREA ON THE POOL OWNERS
 PROPERTY BEFORE DISCHARGING ON CITY PROPERTY.
 * DISCHARGE SHALL NOT FLOOD STREETS OR NEIGHBORING
 PROPERTY.
 * FOR TECHNICAL QUESTIONS, CONTACT O&M SUPERINTENDENT
 STEPHON HARRIS AT [email protected] OR 561-822-2168.
 * FOR STORMWATER DISCHARGE COMPLIANCE QUESTIONS, PLEASE
 CONTACT CHRIS JACKSON, ENVIRONMENTAL COMPLIANCE
 SPECIALIST III, PUBLIC UTILITIES DEPARTMENT, (561)
 822-2062 OR [email protected].
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  