| 2023-01-25 09:37:08 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) THERE IS NO INDICATION OF A SITE PLAN SHOWING THE |
| | PROPOSED LOCATIONS OF THE TENTS |
| | |
| | PER NFPA 1 |
| | |
| | 1.7.12 PLANS AND SPECIFICATIONS. |
| | |
| | 1.7.12.7 PLANS SHALL BE SUBMITTED TO THE AHJ FOR OTHER |
| | CONDITIONS AS DEEMED NECESSARY BY THE AHJ TO DETERMINE |
| | COMPLIANCE WITH THE APPLICABLE CODES AND STANDARDS. |
| | |
| | PLEASE PROVIDE A SITE PLAN. |
| | |
| | |
| | |
| | 2) PLEASE PROVIDE THE TYPE OF EVENT AND IF TABLES AND |
| | CHAIRS ARE PROPOSED PLEASE PROVIDE THAT FLOOR PLAN. |
| | |
| | 1.7.12 PLANS AND SPECIFICATIONS. |
| | |
| | 1.7.12.7 PLANS SHALL BE SUBMITTED TO THE AHJ FOR OTHER |
| | CONDITIONS AS DEEMED NECESSARY BY THE AHJ TO DETERMINE |
| | COMPLIANCE WITH THE APPLICABLE CODES AND STANDARDS. |
| | |
| | |
| | |
| | 3) PLEASE ENSURE THE TENTS ARE A MIN. 10 FT. FROM |
| | BUILDING OR OTHER TENT STAKES LINES. |
| | |
| | NO COOKING, BBQS, OPEN FLAMES NOR PROPANE HEATERS UNDER |
| | THE TENTS |
| | |
| | PER NFPA 1 CH 25 |
| | |
| | 25.2.3 LOCATION AND SPACING. |
| | 25.2.3.1 THERE SHALL BE A MINIMUM OF 10 FT (3050 MM) |
| | BETWEEN STAKE LINES. [101: 11.11.3.1] |
| | |
| | 25.2.3.5 THE PLACEMENT OF TENTS RELATIVE TO OTHER |
| | STRUCTURES |
| | SHALL BE AT THE DISCRETION OF THE AHJ, WITH |
| | CONSIDERATION GIVEN |
| | TO OCCUPANCY, USE, OPENING, EXPOSURE, AND OTHER SIMILAR |
| | FAC TORS. [101: 11.11.3.5] |
| | |
| | PLEASE ENSURE COMPLIANCE AND PROVIDE A NOTE EOF |
| | ACKNOWLEDGMENT. |
| | |
| | |
| | |
| | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |