| Date |
Text |
| 2023-01-25 17:29:09 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 23010901 |
| | 1/25/2023 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS A-1 & EP-1: THE SANITARY RISER SHOWS A |
| | VENT-TO-RIDGE ABOVE THE NEW HAND SINK WHICH DOES NOT |
| | APPEAR TO BE CORRECT GIVEN THE NEW SINK IS ADJACENT TO |
| | A HALF-WALL AND BAR COUNTER WHICH WOULD PROVIDE NO |
| | MEANS OF CONCEALING THE VENT PIPE RUN THROUGH THE OPEN |
| | AIR TO THE ROOF. PLEASE CLARIFY IF THIS IS THE DESIGN |
| | INTENTION OR A DESIGN ERROR- SEC. 107.2.1 WPB. |
| | |
| | 2) EP-1: A SEPARATE PERMIT IS REQUIRED FOR THE GREASE |
| | INTERCEPTOR AND DUE TO A CHANGE IN PROCESS, THE |
| | PLUMBING REVIEW CANNOT BE APPROVED UNTIL AT A MINIMUM |
| | AN APPLICATION IS SUBMITTED. |
| | |
| | GREASE INTERCEPTOR PERMITS ARE REQUIRED TO BE SUBMITTED |
| | PRIOR TO APPROVAL OF THE MAIN PLUMBING PLANS. YOU CAN |
| | SUBMIT AN APPLICATION ???TBD??? (TO BE DETERMINED) IF |
| | YOU DO NOT HAVE A CONTRACTOR SELECTED BY EMAILING A |
| | COMPLETED PERMIT APPLICATION TO [email protected] |
| | . YOU WILL RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD |
| | PLANS. YOU MAY UPLOAD PLANS AND PAY FEES AT A FUTURE |
| | DATE, BUT THE APPLICATION IS REQUIRED AT THIS TIME. WE |
| | RECOMMEND THAT YOU PAY FEES AND UPLOAD PLANS AT THE |
| | SAME TIME. AFTER YOU HAVE THE PERMIT(S) GENERATED, |
| | NOTIFY ME VIA EMAIL AND I WILL CHANGE THE REVIEW STATUS |
| | TO PASS. |
| | |
| | 3) EP1: THE GREASE INTERCEPTOR SHALL ALSO BE REVIEWED |
| | UNDER THIS MASTER PERMIT. PLEASE PROVIDE THE FOLLOWING |
| | ITEMS. |
| | A) MANUFACTURER'S SPECIFICATIONS- SECS.1003.3.5 OR |
| | 1003.3.7 FBC P. |
| | B) EQUIPMENT SCHEDULE INDICATING THE MAKE, MODEL AND |
| | CAPACITY OF THE UNIT. |
| | C) SIZING CALCULATIONS IN ACCORDANCE WITH ASME |
| | A112.14.3, ASME A112.14.4, ASME A112.14.6, CSA B481.3, |
| | OR PDI G101 FOR HYDROMECHANICAL TYPES; OR SEC. 1003.3.7 |
| | FOR GRAVITY TYPES. |
| | D) REVISE THE ISOMETRIC DRAWING OR PROVIDE AN ENLARGED |
| | INTERCEPTOR PIPING DIAGRAM. THE DIAGRAM SHALL SHOW THE |
| | LOCATIONS AND SIZES OF INLETS, OUTLETS, VENTS, |
| | CLEANOUTS, AND FLOW CONTROL VENTING WHERE REQUIRED BY |
| | THE MANUFACTURER. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |