| 2023-01-23 17:36:31 | PETER E VALENTI |
| | BUILDING PLANS EXAMINER II/INSPECTOR |
| | [email protected] |
| | 561 805 6673 |
| | |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC M = FBC MECHANICAL |
| | FBC FG = FBC FUEL GAS |
| | |
| | BUILDING REVIEW DENIED: |
| | |
| | 1.) FBC B 107.2.1, THE ORIENTATION OF STRUCTURE ON PLAN |
| | SHEETS: A-1/D-1, A-2, & E-1, APPEAR TO BE OPPOSITE OF |
| | NORTH INDICATER. PLEASE CONFIRM THAT THE ORIENTATION OF |
| | STRUCTURE ON PLAN SHEETS IS CORRECT AS IS, OR ADJUST |
| | THE STRUCTURES TO CORRELATE WITH THE DIRECTION |
| | INDICATER. |
| | 2.) FBC B 303.3 & FBC B 304, COVER SHEET (CODE SECTION) |
| | STATES THAT THE OCCUPANCY FOR THEIS PROJECT IS B |
| | (BUSINESS), BUT APPEARS TO BE AN A-2. PLEASE REVIEW AND |
| | ADJUST OCCUPANCY. |
| | 3.) FBC B 107.2.1 & TABLE FBC B 1004.1.2, THE OCCUPANCY |
| | LOAD CALCULATIONS ON THE PLAN COVER SHEET INDICATE THE |
| | DINING AREA TO BE AN ASSEMBLY AREA WITHOUT FIXED SEATS |
| | (15 S.F. PER PERSON). HOWEVER, THE PLAN SHEET A-1 |
| | INDICATES ASSEMBLY AREA WITH FIXED SEATS OR WITHOUT |
| | FIXED SEATS CONCENTRATED. PLEASE CLARIFY THE TYPES OF |
| | ASSEMBLY SEATING ON PLAN SHEET A-1 AND REVIEW/ADJUST |
| | THE DINING AREA OCCUPANCY/OCCUPANTS ON THE COVERSHEET |
| | (OCCUPANCY LOAD CALCULATIONS SECTION). |
| | 4.) FBC B TABLE 601/TABLE 705.4, FBC EB 504/505, THE |
| | ALTERATION LEVEL FROM THE FLORIDA EXISTING BUILDING HAS |
| | NOT BEEN IDENTIFIED ON THE COVER SHEET. PLEASE IDENTIFY |
| | THE ALTERATION LEVEL PER THE FLORIDA EXISTING BUILDING |
| | CODE AND REVIEW TABLE 601 OF THE FLORIDA BUILDING CODE |
| | AS THE FIRE RATING OF THE DIMIZING WALLS MAY NEED TO BE |
| | ADJUSTED. |
| | 5.) FBC B 107.2.1 & FBC A 609.4, PLAN SHEET A-2 DETAIL |
| | 4 IS NOT CLEAR AS TO THE HEIGHT REQUIREMENT OF |
| | ACCESSIBLE GRAB BARS. PLEASE CLARIFY ON THIS DETAIL. |
| | 6.) FBC B 107.2.1 & FBC A 606.3, PLAN SHEET A-2 DETAIL |
| | 3 IS NOT CLEAR AS TO MIRROR HEIGHT REQUIREMENTS AND |
| | SINK HEIGHT REQUIREMENTS. PLEASE CLARIFY ON THIS |
| | DETAIL. |
| | 7.) FBC B 107.2.1 & FBC A 902.3, PLAN SHEET A-2 DETAIL |
| | 6 IS NOT CLEAR AS TO ACCESSIBLE COUNTER TOP HEIGHT OF |
| | 34". PLEASE CLARIFY ON THIS DETAIL. |
| | 8.) FBC A 226.2, DISPERSION. DINING SURFACES AND WORK |
| | SURFACES SHALL BE DISPERSED THROUGHOUT THE SPACE OR |
| | FACILITY CONTAINING DINING SURFACES AND WORK SURFACES. |
| | PLEASE SHOW ACCESSIBLE SPACES IN EACH REQUIRED AREA. |
| | 9.) FBC B 107.2.1, FBC A 226.2, FBC A 306.2, & FBC A |
| | 306.3. ON PLAN SHEET A-1, THIS LOCATION APPEARS TO BE |
| | SET BACK IN A CORNER, DOES NOT APPEAR TO HAVE THE |
| | REQUIRED ACCESS/TURN AROUND SPACE, AND DOES NOT APPEAR |
| | TO HAVE THE REQUIRED KNEE & TOE SPACE. PLEASE SHOW A |
| | DIFFERENT LOCATION FOR ACCESSIBLE SPACE AT COUNTER. AND |
| | SHOW REQUIRED CLEARANCES. |
| | 10.) FBC B 107.2.1, PLEASE PROVIDE |
| | DETAILS/SPECIFICATIONS FROM MANUFACTURER OF THE THE |
| | GLUE LAM BEAM PROPOSED ON PLAN SHEET A-1. |
| | 11.) FBC B TABLE 2902.1, THE NUMBER OF PLUMBING |
| | FIXTURES APPEARS TO BE TOO LOW. PLEASE EVALUATE THE |
| | MINIMUM NUMBER REQUIRED PER FBC B TABLE 2902.1. |