| Plan Review Notes For Permit 23010896 |
| Permit Number |
23010896 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-02-17 12:45:55 | REMODEL | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) THE WINDOW AND DOOR LOCATION PLAN DOES NOT MATCH ALL | | | OF THE OTHER FLOOR PLANS (BEDROOM #3 EXTERIOR DOORS) | | | ALL FLOOR PLANS NEED TO MATCH. FBC 107 | | | | | | 2) SIGNED AND SEALED DRAWINGS (A-100, A-101, A-102, | | | A-103) DO NOT SHOW AS DIGITALLY SIGNED IN ADOBE READER | | | - SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | | DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN | | | ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL | | | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A | | | SPECIFIC TYPE OF E-SIGNATURE). | | | | | | |
|