| 2023-01-23 13:28:47 | 1ST BUILDING REVIEW |
| | RESULTS: CORRECTIONS NEEDED |
| | |
| | CHRISTOPHER S. THROOP, CBO, BN, PX, CFM |
| | PLANS EXAMINER II |
| | CITY OF WEST PALM BEACH |
| | (561) 805-6726 |
| | [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | NFPA 70 2017 EDITION NEC 2017 |
| | |
| | ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT: |
| | |
| | NOTICE: A SEPERATE PERMIT IS REQUIRED FOR THE ACCESSORY |
| | STRUCTURE. E-MAIL A PERMIT APPLICATION TO: |
| | [email protected] |
| | ALL PLANS SHALL REMAIN UNDER PERMIT 23010809 |
| | |
| | NOTICE: AN ELEVATION CERTIFICATE (EC) WAS SUBMITTED FOR |
| | REVIEW. THE CITY DOES NOT REVIEW EC'S FOR PROPERTIES |
| | THAT ARE NOT LOCATED IN SPECIAL FLOOD HAZARD AREAS. |
| | THIS PROPERTY IS LOCATED IN ZONE X. |
| | |
| | 1. PROVIDE A SITE DRAINAGE PLAN PER FBC R401.3 |
| | IT SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND |
| | INCLUDED BOUNDARY LINE SURVEY. |
| | FBC R401.3 SITE DRAINAGE |
| | |
| | 2. PROVIDE AN ENERGY SUBMITTAL RESIDENTIAL (RE) FOR THE |
| | MAIN DWELLING UNIT. |
| | R401.2COMPLIANCE. |
| | SECTION R405 AND THE PROVISIONS OF SECTIONS R401 |
| | THROUGH R404 LABELED MANDATORY. |
| | |
| | 3.IDENTIFY THE CEILING AND WALL INSULATION TYPE AND |
| | R-VALUE FOR THE ACCESSORY STRUCTURE ON THE PLANS. |
| | 107.2 CONSTRUCTION DOCUMENTS SHALL BE IN ACCORDANCE |
| | WITH SECTIONS107.2.1 THROUGH 107.2.5. |
| | |
| | 4.PROVIDE A WINDOW AND DOOR FLASHING DETAIL OR THE |
| | SPEC. SHEET OF A FLUID APPLIED MEMBRANE. |
| | R703.4 |
| | APPROVED METAL FLASHING, VINYL FLASHING, SELF-ADHERED |
| | MEMBRANES AND MECHANICALLY ATTACHED FLEXIBLE FLASHING |
| | SHALL BE APPLIED SHINGLE-FASHION OR IN ACCORDANCE WITH |
| | THE MANUFACTURER???S INSTRUCTIONS. |
| | |
| | 5. PROVIDE A WINDOW AND DOOR SCHEDULE. |
| | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| | 107.2.5. |
| | |
| | 5.PROVIDE A COPY OF THE CURRENT FLORIDA PRODUCT |
| | APPROVALS APPROVED UNDER THE 2020 FBC, FOR THE PROPOSED |
| | WINDOWS AND DOORS. (BOTH STRUCTURES) |
| | FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS, |
| | EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS. |
| | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| | |
| | 6.PROVIDE LOCATION OF ATTIC ACCESS PER R807.1.7. |
| | R807.1.7 BUILDINGS WITH COMBUSTIBLE CEILING OR ROOF |
| | CONSTRUCTION SHALL HAVE AN ATTIC ACCESS OPENING TO |
| | ATTIC AREAS THAT HAVE A VERTICAL HEIGHT OF 30 INCHES |
| | (762 MM) OR GREATER OVER AN AREA OF NOT LESS THAN 30 |
| | SQUARE FEET (2.8 M2). |
| | |
| | 3.PROVIDE SMOKE ALARMS. |
| | FBC 1104.1SMOKE ALARMS IN EXISTING PORTIONS OF A |
| | BUILDING. |
| | SMOKE ALARMS |
| | R314.2.2ALTERATIONS, REPAIRS AND ADDITIONS. |
| | WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A |
| | PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE |
| | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL |
| | DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS |
| | LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC R314. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |