| Plan Review Notes For Permit 23010885 |
| Permit Number |
23010885 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2023-03-17 10:23:15 | 2ND REVIEW FMC | | | PERMIT: 23010885 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | GARAGE APPROVED. ME 3/20/2023 | | | | | | 1) THE BACKDRAFT DAMPER SHOWN ON SHEET M5.2 DETAIL 15 | | | IS NOT CODE COMPLIANT. THE BACKDRAFT DAMPER IS AN | | | INTEGRAL PART OF THE EXHAUST DUCT TERMINATION SEE CODE | | | SECTION BELOW. | | | | | | M1502.3 DUCT TERMINATION. EXHAUST DUCT TERMINATIONS | | | SHALL BE EQUIPPED WITH A | | | BACKDRAFT DAMPER. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|