| 2023-02-21 11:44:19 | SFR REMODEL |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | |
| | 1) DRAWING S-3 - "STRUCTURAL NOTES" SHOW FBC 2017 USING |
| | ASCE 7-10 FOR THE WIND DESIGN - SHOULD BE FBC 2020 |
| | USING ASCE 7-16 FOR THE WIND DESIGN. FBC CHAPTER 35 |
| | |
| | 2) PLEASE PROVIDE A SURVEY SHOWING FEMA BASE FLOOD |
| | ELEVATION AND THE DELINEATION LINE BETWEEN THE AE6 AND |
| | THE AE7 FLOOD ZONES. |
| | |
| | 3) THE JOB IS A SUBSTANTIAL IMPROVEMENT - FBC EXISTING |
| | BUILDING 701.3 FLOOD HAZARD AREAS. |
| | IN FLOOD HAZARD AREAS, ALTERATIONS THAT CONSTITUTE |
| | SUBSTANTIAL IMPROVEMENT SHALL REQUIRE THAT THE BUILDING |
| | COMPLY WITH SECTION 1612 OF THE FLORIDA BUILDING CODE, |
| | BUILDING, OR SECTION R322 OF THE FLORIDA BUILDING CODE, |
| | RESIDENTIAL, AS APPLICABLE. |
| | FBC EXISTING BUILDING SECTION202 - SUBSTANTIAL |
| | IMPROVEMENT. FOR THE PURPOSE OF DETERMINING COMPLIANCE |
| | WITH THE FLOOD PROVISIONS OF THIS CODE, ANY REPAIR, |
| | ALTERATION, ADDITION, OR IMPROVEMENT OF A BUILDING OR |
| | STRUCTURE, THE COST OF WHICH EQUALS OR EXCEEDS 50 |
| | PERCENT OF THE MARKET VALUE OF THE STRUCTURE, BEFORE |
| | THE IMPROVEMENT OR REPAIR IS STARTED. |
| | |
| | 4) THE ENTIRE BUILDING WILL NEED TO BE ELEVATED TO 2 |
| | FEET ABOVE THE FEMA BASE FLOOD ELEVATION - |
| | ORDINANCE NO. 4729-17 SECTION 4 SEC. 18-33 - TECHNICAL |
| | AMENDMENTS TO FLORIDA BUILDING CODE, RESIDENTIAL. |
| | |
| | (A) R322.2.1 ELEVATION REQUIREMENTS. |
| | |
| | 1. BUILDINGS AND STRUCTURES IN FLOOD HAZARD AREAS NOT |
| | DESIGNATED AS COASTAL A ZONES |
| | SHALL HAVE THE LOWEST FLOORS ELEVATED TO OR ABOVE THE |
| | BASE FLOOD ELEVATION PLUS TWO |
| | FEET OR THE DESIGN FLOOD ELEVATION, WHICHEVER IS |
| | HIGHER. |